background image

Cambridge Air Solutions 

18 

SA-Series Technical Manual

      a.  Turn the burner service switch to the “OFF” 

position and allow the Discharge Air 

Temperature Sampling Box time to cool.

       b.  Turn blower service switch to “OFF” position.
       c.  Open the control enclosure door.
      d.  Remove the access cover from the Discharge 

Air Temperature Sampling Box and remove the 

two mounting screws from the DTS. Refer to the 

Individual Component Description Section (page 

38-40) for additional information.

      e.  Carefully remove the DTS from the sampling 

box, turn it over and adjust the DTS calibration 

potentiometer shown in the drawing. To raise the 

discharge temperature, adjust the potentiometer 

90˚ counterclockwise. 

       f.  Carefully reinstall the DTS. Replace the 

Discharge Air Temperature Sampling Box cover, 

and close the unit access doors.

      g.  Turn the blower and burner service switches to 

the “LOCAL” position. After a delay for the 

prepurge and igniter warm-up, the burner will 

light.

      h.  Wait for the discharge temperature and manifold 

pressure to stabilize. Do not rush this step.

      i.  Repeat steps 2 through 4 until manifold pressure 

and discharge temperature comply with guidelines 

of Calibration Check procedure step 5 (page 16).

      j.  Reinstall the amplifier that was removed in step 1.

MAINTENANCE INSTRUCTIONS

BELT TENSIONING (SA350 ONLY)

Using a Browning Belt Tension Checker and a straight 

edge, verify proper belt tension to a center span 

deflection of 1/4" for 2-3 lbs. for new belts or 1-2 lbs. 

for used belts.
Periodic belt adjustments may be required. Indications 

of loose belts include barking or squealing when blower 

starts.

BLOWER CLEANING

The blower wheel should be examined for accumulation 

of dust on the blades. These surfaces must be kept clean. 

Dirt accumulation will result in significant air flow 

reduction and/or possible imbalance of the blower wheel. 

CAUTION:

Prolonged imbalance can result in catastrophic  

failure of the blower wheel and other related  

components.

BURNER CLEANING

The Cambridge Air Solutions burner is for the most part 

self-cleaning. However, if the application is extremely 

dirty or dusty, it may become necessary to periodically 

clean the burner. Remove and clean the burner in 

accordance with the following recommended procedures:

1.   Turn off the disconnect switch (by others).  Close the 

manual gas supply shut-off valve.

2.  Loosen the union in the gas train.

3.   Disconnect the ignition cable from the burner and 

remove the flame rod and the igniter.

4.   Examine the flame rod ceramic for cracks and replace 

if necessary. Clean the flame rod element with emery 

cloth to remove oxidation.

5.   Remove fasteners that secure burner to housing. The 

burner will then be free to slide out.

6.   Clean burner by back-flushing using high pressure 

air (40-80 PSI). Continue back flushing until dust 

particles are completely expelled from burner.

7.   Reinstall burner using above steps in reverse order.

GAS TRAIN LEAK CHECK

Periodically check the gas control assembly, internal and 

external piping for leaks. Refer to the Gas Train Leak 

Check procedure (page 16). All relief vents on the gas 

controls should be checked for blockage (gas pressure 

regulators and pressure switches).

Содержание Blow-Thru SA Series

Страница 1: ... and maintenance instructions thoroughly before installing or servicing this equipment FOR YOUR SAFETY The use and storage of gasoline or other flammable vapors and liquids in open containers in the vicinity of this appliance is hazardous FOR YOUR SAFETY If you smell gas 1 Open windows 2 Don t touch electrical switches 3 Extinguish any open flame 4 Immediately call your gas supplier Made in the US...

Страница 2: ...Manufacturer does not warrant Products if they are abused improperly operated or maintained subjected to abnormal wear and tear damaged due to improper gas or electric service damaged in transit or that have been repaired or modified by others without Manufacturer s written authorization Buyer shall have no right to enforce this Warranty unless it has complied with all of its obligations under the...

Страница 3: ...em Overview 4 Accessory Identification 4 Heater Operation 5 Heater Configuration 5 Roof Top Mounting 6 Thru Wall Mounting 8 Under Roof Mounting 10 Gas Piping 12 Electrical Wiring 13 Start up Instructions 14 Shutdown Instructions 17 Calibration Procedure 17 Operating Instructions 19 Operating Sequence 19 TSS Controller 20 Troubleshooting Instructions 29 Troubleshooting Guide 29 Reference 35 Electri...

Страница 4: ...acity It should be noted that this can be accomplished by taking into account through standard engineering methods the structure s designed infiltration rate by providing properly sized relief openings or by interlocking a powered exhaust system or by a combination of these methods If the failure or malfunction of this heater creates a hazard to other fuel burning equipment in the building e g whe...

Страница 5: ...fect the desired air distribution pattern of the heater WARNING It is recommended the heater mounting structure be reviewed and approved by a qualified structural engineer and the roof manufacturer before installing this equipment WARNING To prevent contaminated air from being drawn into the heater install the heater s inlet at least 10 feet from any building exhaust process exhaust sewer stacks o...

Страница 6: ...CATION Roof Top Mounting RH UNIT AMS MC DE DD Thru Wall Spiral Mounting Thru Wall Mounting RH IC UNIT DE AMS Adjustable Mounting Stand DD Discharge Duct DE Directional Elbows IC Inlet Collar IT Inlet Transition MC Mounting Curb RH Rain Hood Component Identification Under Roof Mounting IT UNIT DE ...

Страница 7: ...e heaters on and off in response to the rise and fall of the space temperature The heater will discharge air at the temperature selected up to 160ºF The operating thermostat is typically located near the perimeter of the building in a location which is out of the direct path of the heated discharge air insulated from cold surfaces and shielded from cold drafts created by air infiltrating the build...

Страница 8: ...of manufacturer s recommendations IMPORTANT The roof curb and mounting stands should be installed so that the heater will mount level Cambridge recommends mounting the heater 24 off the roof surface in areas where snow accumulation could impact heater operations 3 Lower the discharge duct through the mounting curb and the roof opening and secure the counterflashing to the mounting curb 4 Use a cra...

Страница 9: ...CLOSURE ADJUSTABLE MOUNTING STAND BLOWER ACCESS PANEL CONTROL WIRING CONDUIT REMOTE CONTROL STATION THERMOSTAT CONTROLS INCOMING POWER BY OTHERS SA250 SA350 BLOWER ACCESS PANEL SA250 TYPICAL INSTALLATION ROOF TOP MOUNTING NOTES TREATED TIMBER REQUIRED UNDER MOUNTING CURB AND STAND TO SECURE AND LEVEL UNIT SECURE MOUNTING STAND TO TIMBER WITH WOOD LAG SCREWS AS SHOWN MOUNTING STAND CONSTRUCTION 12 ...

Страница 10: ...e hanging brackets on the unit Locate the hanging rods so that the weep holes provided in the rain hood are located a minimum of 3 beyond the outside wall surface 4 Install the hanging brackets on the heater 5 Use a forklift or comparable lifting device to raise and position the heater Take precautions to prevent equipment damage dents and or scratches when the heater is being lifted into position...

Страница 11: ...nual 9 Cambridge Air Solutions TYPICAL INSTALLATION THRU WALL MOUNTING HANGING ROD DETAIL HANGING BRACKET DETAIL HANGING ROD WASHER WASHER NUT SHIPPING POSITION DOUBLE NUT SA250 SA350 HANGING RODS NUTS AND WASHERS BY OTHERS ...

Страница 12: ...ss exhaust sewer stacks or other sources that would allow contaminants to be drawn into the heater Consult local codes for additional references 1 Install the accessories for roof intake by others 2 Install the hanging brackets on the heater 3 Install hanging rods to adequate ceiling supports and align with the hanging brackets on the heater 4 Use a forklift or comparable lifting device to raise a...

Страница 13: ...OTHERS INCOMING POWER BY OTHERS HANGING ROD THERMOSTAT CONTROLS REMOTE CONTROL STATION CONTROL WIRING CONDUIT BY OTHERS INSULATED INLET DUCT BY OTHERS INSULATED INLET ELBOW BLOWER ACCESS PANEL SA350 SA250 TYPICAL INSTALLATION UNDER ROOF MOUNTING HANGING ROD DETAIL HANGING BRACKET DETAIL SA250 SA350 HANGING RODS NUTS AND WASHERS BY OTHERS HANGING ROD WASHER WASHER NUT SHIPPING POSITION DOUBLE NUT ...

Страница 14: ...the gas piping to the unit in accordance with local codes or in their absence in accordance with the National Fuel Gas Code ANSI Standard Z223 1 or the CAN CSA B149 Installation Codes IMPORTANT A 1 8 NPT tap is supplied with the heater for measuring the gas supply pressure If the gas supply pressure exceeds that indicated on the nameplate the installer must install a 1 8 NPT tap and high pressure ...

Страница 15: ...cause infiltration air can affect the sensor when the door is closed and the sensor may not adequately sense the temperature when the door is open In this application the sensor should be located on the first column in from the outside wall CAUTION Observe special notes and instructions on Wiring and Connection Diagrams regarding sensor installation The wiring for any temperature sensors mounted r...

Страница 16: ...the unions in the gas piping located at the burner and just external to the heater housing are tight 8 If inlet ducting is utilized determine the time required to purge it with four 4 air changes and select a pre purge time that will accommodate this time Utilize jumper settings on the Multi functional PC Board to set the Purge Timer to 2 4 8 16 or 32 seconds as applicable ADJUSTMENT TIMER PREPURG...

Страница 17: ...rner service switch to the LOCAL position After a delay for prepurge and igniter warm up the burner will light Allow 15 seconds for the low fire start to time out 9 Observe the manometer reading and compare to the manifold pressure determined Step 7 If the manifold pressure reading does not equal this value adjust the control regulator until the proper manifold pressure is obtained 10 Turn the blo...

Страница 18: ...ls 21 and 22 The dial should be set to 160 F IMPORTANT The heater access doors must be closed for the remaining portion of this test 3 Turn the blower and burner service switches to the LOCAL position After a delay for prepurge and igniter warm up the burner will light Allow 15 seconds for the low fire start to time out 4 Monitor the discharge temperature until it stabilizes Do not rush through th...

Страница 19: ...ner ignition after a delay for pre purge and igniter warm up 5 Reset the thermostat to the desired space temperature 6 Reinstall jumper to Normal Mode 7 Service switches should be in REMOTE FINAL HEATER PREPARATION 1 Perform visual inspection of all wiring and gas valve plugs to ensure they have been properly replaced 2 Remove all test instrumentation 3 Replace and fasten all covers and panels Clo...

Страница 20: ... Periodic belt adjustments may be required Indications of loose belts include barking or squealing when blower starts BLOWER CLEANING The blower wheel should be examined for accumulation of dust on the blades These surfaces must be kept clean Dirt accumulation will result in significant air flow reduction and or possible imbalance of the blower wheel CAUTION Prolonged imbalance can result in catas...

Страница 21: ...tinues to run until turned off HEATING MODE 1 Mode switch in HEATING position CE Smart only 2 Thermostat or interlock calls for heat 3 Optional motorized inlet damper opens 4 Blower motor starts 5 Airflow switch closes 6 Entering air thermostat closes when inlet temperature is below setpoint after the prepurge delay 7 Igniter warm up timing 8 Gas valve opens 9 Burner lights 10 Igniter is de energi...

Страница 22: ...tic adjustment for Daylight Saving Time Nine Holiday Setback Periods for temporary setback operation Temperature Calibration for accurate temperature control Capacitor backup maintains current time and day of week for power loss of up to 96 hours EEPROM storage maintains schedules and temperature settings indefinitely The thermistor enclosure SH 1 is packed inside the Remote Control Station for sh...

Страница 23: ... the DAY OF WEEK button while pressing the UP or the DOWN button until the light for the current day is illuminated 2 Press and hold the TIME button while pressing the UP or the DOWN button until the current time is displayed 3 Press and hold the MONTH DAY button while pressing the UP or the DOWN button until the current date is displayed 4 Press and hold the YEAR button while pressing the UP or t...

Страница 24: ...he OFF time schedule is in effect See SETTING SCHEDULES for instructions on setting the ON and OFF schedules With the keyswitch in the SUMMER VENTILATION position the heater fan will run based on the time schedule with no temperature control HEATING MODE ON Time Schedule The HEATING mode requires two temperature settings When the temperature drops below the HEAT ON setting the heater will turn on ...

Страница 25: ...by the VENT MODE light on the TSS Controller being illuminated Before attempting to program the schedule determine the planned time periods for HEAT ON and SETBACK OFF for the HEATING mode and the planned ON and OFF time periods for the Ventilation mode The time that it takes to recover from the SETBACK temperature to the HEAT temperature must also be taken into consideration for the ON time in th...

Страница 26: ... 4 On 5 Off 5 On 6 Off 6 On 7 Off 7 On 8 Off 8 On 9 Off 9 On 10 Off 10 On 11 Off 11 On 12 Off 12 On 13 Off 13 On 14 Off 14 SUMMER VENTILATION SCHEDULE Cycle Time AM PM Day On M F Off M F On 1 Off 1 On 2 Off 2 On 3 Off 3 On 4 Off 4 On 5 Off 5 On 6 Off 6 On 7 Off 7 On 8 Off 8 On 9 Off 9 On 10 Off 10 On 11 Off 11 On 12 Off 12 On 13 Off 13 On 14 Off 14 ...

Страница 27: ...s and bold the TIME button while pressing the UP or the DOWN button to scroll to the desired OFF time for Monday through Friday 6 If Monday through Friday is the only schedule required proceed to Step 14 If any additional programming is required proceed with the following steps Remember that subsequent program cycles must not overlap with the ON and OFF times set above 7 Press the UP button once t...

Страница 28: ...red program cycles have been entered 14 Press the SETBACK SCHEDULE EXIT button to exit the scheduling program 15 Verify that the correct current time and light for day of the week are still displayed HOLIDAY SETBACK SCHEDULE The Holiday Setback Schedule overrides the normal schedule and holds the space at the SETBACK temperature The TSS Controller allows up to nine holiday periods Holiday Start Da...

Страница 29: ...the UP or the DOWN button to scroll to the desired holiday start date 4 Press the UP button once to step to the first holiday end date cycle HEd1 5 Press and hold the MONTH DAY button while pressing the UP or the DOWN button to scroll to the desired holiday end date NOTE Holiday end date must be at least one day after holiday start date 6 Repeat steps 2 5 until all required holiday cycles have bee...

Страница 30: ...lows the displayed temperature to be offset either above or below the actual sensed temperature Be sure to use an accurate temperature meter for making this correction 1 Press and hold the HEAT ON and HEAT OFF buttons while pressing the UP or the DOWN button until the correct temperature is displayed A period after the F will indicate the Calibration Mode 2 Pressing the UP or the DOWN button will ...

Страница 31: ...ge b Blown control fuse c Defective transformer a Check disconnect and supply fusing b Replace control fuse c Replace transformer 7 Class II Transformer a No output voltage b Defective transformer a Check supply voltage b Replace transformer 8 Multi Functional PC Board a No input voltage on Terminal G RCS b Improper wiring c Defective board a Check voltage in RCS b Check wiring c Replace multi fun...

Страница 32: ...pickup ports e Replace switch 5 Flame Safeguard Relay a No input voltage b Defective FSR a Check wiring b Replace FSR III BLOWER RUNS NO HEAT FLAME SAFETY RELAY LOCKS OUT 1 Igniter a No current open igniter b No voltage During trial for ignition a Check igniter current b Check FSR output to igniter 2 High Limit a High limit tripped a See Problem Number VI page 32 3 Gas Valve a No input voltage b G...

Страница 33: ...imum fire on modulating valve c Tighten all ground points d Remove jam nuts from Flame Rod Reassemble with terminal located between jam nuts on Flame Rod e Replace burner 5 Flame Safeguard Relay a Defective FSR a Replace FSR 6 High Limit a High limit contact intermittent a Replace high limit V BLOWER RUNS UNIT HEATS SHORT CYCLES WITHOUT RESETTING 1 Air Flow Switch a Blower running backwards SA350 ...

Страница 34: ...tat in cold draft relocate a2 Thermostat not satisfied turn down b Reduce differential setting c Replace thermostat 2 Burner Service Switch a Switch in LOCAL position a Place switch in REMOTE position 3 Auxiliary Control a Auxiliary contacts closed a Check auxiliary circuit wiring and contacts 4 Misunderstood Control System Operation a Control system doesn t function as expected a Review control s...

Страница 35: ...I Transformer a No voltage output to amplifier a1 Check for short in modulating valve coil a2 Replace transformer 2 Modulating Valve a Valve coil is open or shorted b Plunger jammed c Ruptured main or balancing diaphragm a Replace valve if coil resistance is less than 40 Ω or greater than 85 Ω b Replace valve c Replace valve 3 Amplifier a No output voltage to valve a With the wire removed from ter...

Страница 36: ...efective regulator a Enlarge vent piping size or reduce vent piping length b Replace regulator 2 Amplifier a Hunting b Temperature control system out of calibration c Defective amplifier a Adjust sensitivity control dial counter clockwise b Perform appropriate calibration procedure page 17 c Replace amplifier 3 Space Temperature Selector CE SmartTM a Induced voltage in field wiring a Utilize shiel...

Страница 37: ...SA Series Technical Manual 35 Cambridge Air Solutions REFERENCE ELECTRICAL CONTROL ENCLOSURE SA350 SA250 ...

Страница 38: ...R Flame Safeguard Relay HSI Symbol Description FU1 Fuse 24 Volt Control HL High Limit IG Ignitor LFS Low Fire Start LTC Low Temperature Cutout M Motor MS Motor Starter MV Modulating Valve PCB Printed Circuit Board Symbol Description PT Purge Timer R1A B C Relays Gas Valve R1D Relay Thermostat Control RC Resistor Calibration SOV Shut Off Valve Gas SW1 Service Switch Fan SW2 Service Switch Heat T1 M...

Страница 39: ...igh Limit IG Ignitor LFS Low Fire Start LTC Low Temperature Cutout M Motor MS Motor Starter MV Modulating Valve OL Overload Relay OTS Override Timer Switch PCB Printed Circuit Board PT Purge Timer R1A B C Relays Gas Valve R1D Relay Thermostat Control Symbol Description R2 Relay Makeup Air Mode RC Resistor Calibration RES Resistor Thermostat Override RTS Remote Temperature Sensor SOV Shut Off Valve...

Страница 40: ...Cambridge Air Solutions 38 SA Series Technical Manual REFERENCE ELECTRICAL CONNECTION DIAGRAM ...

Страница 41: ...l s Series 44 modulation controls The discharge temperature sensor which is mounted in the discharge duct transmits a resistance signal back to the amplifier that corresponds to the discharge temperature The amplifier creates a voltage output to drive the modulating valve to maintain the preselected temperature The system can be operated either intermittently as a space heater at maximum discharge...

Страница 42: ...sured with a DC microammeter The reading should be steady and between 2 0 and 6 0 microamps μA FLAME SAFEGUARD RELAY FSR The flame safeguard relay supplies 24 Volts AC to the igniter for 4 seconds before the gas valve is energized If the burner does not light flame is not established within 7 seconds this control will lock out gas flow until the control is reset If flame signal is lost during burn...

Страница 43: ...0 45 50 or 55 F in ventilation mode or b the gas valve fails to remain energized during a heating cycle 3 The EAT Entering Air Thermostat circuit functions automatically to turn off the burner when the outdoor temperature reaches the EAT setpoint 45 50 55 57 5 60 62 64 66 68 or 70 F 4 The PT Purge Timer circuit function is preset at the factory to provide four air changes within the heater cabinet...

Страница 44: ...ses Compliance Requirements The following are required for Cambridge heaters to comply with Standard 90 1 Controls Section 6 4 3 Total airflow of all heaters less than 10 000 cfm The Cambridge CE SmartTM System will meet the standard A properly configured building DDC system with the necessary programming for zone control automatic shutdown and setback can also meet the standard Units intended to ...

Страница 45: ...SA Series Technical Manual 43 Cambridge Air Solutions MAINTENANCE LOG Model No _____________ Serial No _______________________ Date Activity Technician ...

Страница 46: ...Cambridge Air Solutions 44 SA Series Technical Manual MAINTENANCE LOG Model No _____________ Serial No _______________________ Date Activity Technician ...

Страница 47: ...es the right to change specifications modify the design and or substitute equivalent materials without notice as the result of code requirements product enhancements ongoing research development and vendor changes beyond our control ...

Страница 48: ...760 Long Road Crossing Dr Chesterfield MO 63005 Phone 636 532 2233 800 899 1989 Fax 636 530 6133 www cambridgeair com ...

Отзывы: