![Cambium PTP 450 series Скачать руководство пользователя страница 92](http://html1.mh-extra.com/html/cambium/ptp-450-series/ptp-450-series_user-manual_3587321092.webp)
Grounding and lightning protection
2-72
ptp-450 (July 2014)
Assess locations on masts, towers and buildings to determine if the location is in Zone A or Zone B:
Zone A: In this zone a direct lightning strike is possible. Do not mount equipment in this zone.
Zone B: In this zone, direct EMD (lightning) effects are still possible, but mounting in this zone significantly
reduces the possibility of a direct strike. Mount equipment in this zone.
Never mount equipment in Zone A. Mounting in Zone A may put equipment, structures and life at risk.
General protection requirements
To adequately protect a PTP 450 installation, both ground bonding and transient voltage surge suppression are
required.
Basic requirements
The following basic protection requirements must be implemented:
The equipment must be in ‘Zone B’ (see
on page
The BHM must be grounded to the supporting structure.
A surge suppression unit (600SS) must be installed close to the BHS.
The distance between the BHS and 600SS should be kept to a minimum.
The drop cable length between the BHS and 600SS must be less than 600 mm.
A surge suppression unit (600SS) must be installed within 600 mm (24 in) of the point at which the power
cable enters the building or equipment room.
The drop cable must be grounded at the building entry point.
The drop cable must not be laid alongside a lightning air terminal.
All grounding cables must be a minimum size of 10 mm
2
csa (8AWG), preferably 16 mm
2
csa (6AWG), or 25
mm
2
csa (4AWG).
Grounding cable requirements
When routing, fastening and connecting grounding cables, the following requirements must be implemented:
Grounding conductors must be run as short, straight, and smoothly as possible, with the fewest possible number
of bends and curves.
Grounding cables must not be installed with drip loops.
All bends must have a minimum radius of 203 mm (8 in) and a minimum angle of 90° (
). A diagonal
run is preferable to a bend, even though it does not follow the contour or run parallel to the supporting
structure.
All bends, curves and connections must be routed towards the grounding electrode system, ground rod, or
ground bar.
Grounding conductors must be securely fastened.
Braided grounding conductors must not be used.
Approved bonding techniques must be used for the connection of dissimilar metals.
Содержание PTP 450 series
Страница 1: ...Cambium PTP 450 User Guide System Release 13 2...
Страница 20: ......