Grounding the PTP 820C
Loosen the nut, plain washer, and
serrated washer from the GND
stud, using the metric offset
hexagon key and the wrench.
1
2
Place the cable lug
supplied with the grounding
kit in place on the screw
and secure the cable lug.
3
Connect the second side of
the GND cable to the main
or terminal ground bar of
the site.
4
Perform a resistance test
between the 2 lugs of the
GND cable and verify that
the result is 0-2 ohms.
Notes:
The unit’s earthing screw terminal shall be permanently connected to protective earth in a building installation in accordance with
applicable national code and regulations by a service person.
A 2-pole circuit breaker, a branch circuit protector, suitably certified in accordance with applicable national code and regulations,
rated maximum 20A, shall be installed for full power disconnection in a building installation.
Any outdoor antenna cable shield shall be permanently connected to protective earth in a building installation.