Rejuvenation Series Spas
LTR50001131, Rev. A
Pr
eparing f
or
Your Ne
w P
or
tab
le Spa
www.calspas.com
5
All 240V spas must be permanently connected (hard
wired) to the power supply. See the wiring diagram
on page 6.
These instructions describe the only acceptable
electrical wiring procedure . Spas wired in any
other way will void your warranty and may
result in serious injury .
When installed in the United States, the electrical
wiring of this spa must meet the requirements of
NEC 70 and any applicable local, state, and federal
codes.
The electrical circuit must be installed by an
electrical contractor and approved by a local
building or electrical inspector .
Failure to comply with state and local codes
may result in fire or personal injury and will be
the sole responsibility of the spa owner .
The power supplied to the spa must be on a dedicated
GFCI protected circuit as required by NEC 70 with no
other appliances or lights sharing the power.
Use copper wire with THHN insulation. Do not use
aluminum wire.
Use the table on the next page to determine your
GFCI and wiring requirements.
Wire runs over 85 feet must increase wire gauge
to the next lower number. For example: A normal
50 amp GFCI with four #6 AWG Copper wires run
over 85 feet would require you to go to four #4 AWG
copper wires.
240 Volt Electrical Installation
GFCI and Wiring Requirements
GFCI Required
Wires Required
One 40 amp GFCI
Four #8 AWG copper wires
Testing the GFCI Breaker
Test the GFCI breaker prior to first use and periodically when the spa is powered. To test the GFCI breaker
follow these instructions (spa should be operating):
Press the TEST button on the GFCI. The GFCI will trip and the spa will shut off.
1.
Reset the GFCI breaker by switching the breaker to the full OFF position, wait a moment, then turn the
2.
breaker back on. The spa should have power again.
Содержание Rejuvenation Series
Страница 1: ...LTR50001131 Rev A 1 2 13...