THS3001-1020   Printed in Canada

CX Series

Special Notes

CAUTION

CAUTION. 

This document presents the minimum requirement pertaining 

to the installation, operation, and maintenance of the respective 

equipment as required by the manufacturer only. Any additional 

considerations, including but not limited to any design consideration, 

in-service inspection, and fitness-for-service assessment for all pressure 

boundary components to meet any safety principles and local jurisdictional 

regulatory requirements, shall be the responsibility of the user.

ELECTRIC SHOCK HAZARD. 

All electric heating equipment installations 

must be performed by qualified personnel in accordance with the local 
electrical codes and standards and must be effectively grounded to 
eliminate shock hazard.

WARNING

FIRE/EXPLOSION HAZARD FOR EXPLOSIVE ATMOSPHERE HEATERS. 

This heater shall be used with protection controls as follows:

Liquid Immersion Applications

a.  Liquid level control to maintain all the heating elements totally 

immersed at all times, in conjunction with temperature controls to limit 

the liquid temperature below the maximum allowable process design 

temperature. 

b.  Terminal box internal surface temperature control to limit the surface 

temperature of the terminal box

c.  Heater flange surface temperature control to limit the surface 

temperature of the  flange.

d.  Heating elements sheath temperature controls to limit to the maximum 

allowable sheath design temperature

e.  Earth fault or earth leakage current protection device to protect against 

arcing and sparking during an earth fault.

Gaseous and/or vapour phase immersion applications

a.  Heating elements sheath temperature controls to limit to the maximum 

allowable sheath design temperature.

b.  Terminal box internal surface temperature control to limit the surface 

temperature of the terminal box

c.  Heater flange surface temperature control to limit the surface 

temperature of the flange.

d.  Earth fault or earth leakage current protection device to protect against 

arcing and sparking during an earth fault.

CAUTION

Immersion Heaters

ISO 9001

Installation, Operation, & Maintenance Instructions

For CE/ATEX and IECEx Models. Models with 

Increased Safety (Type eb) Protection Method

Содержание CX Series

Страница 1: ...t all times in conjunction with temperature controls to limit the liquid temperature below the maximum allowable process design temperature b Terminal box internal surface temperature control to limit the surface temperature of the terminal box c Heater flange surface temperature control to limit the surface temperature of the flange d Heating elements sheath temperature controls to limit to the m...

Страница 2: ...th the following specific conditions of use 1 The heater shall be installed with electrical safety devices as described in the Installation Operating and Maintenance manual and in accordance with local codes and standards 2 It is the user s responsibility to connect the installed temperature sensors to safety devices as defined in IEC 60079 0 that are fail safe and can only be reset manually The t...

Страница 3: ...3 3 TABLE OF CONTENTS A Diagrams 4 B Description 6 C Installation 7 D Operation 8 E Maintenance 8 ...

Страница 4: ... or Vertical Immersion Heater Round Box IP66 Stilted TERMINAL BOX TEMPERATURE SENSOR THERMOCOUPLE OR RTD TERMINAL BOX SENSOR THERMOCOUPLE OR RTD A DIAGRAMS TERMINAL BOX TEMPERATURE SENSOR THERMOCOUPLE OR RTD INCREASED SAFETY TERMINAL BOX ROUND RATED IP66 AVAILABLE IN PAINTED STEEL OR STAINLESS STEEL INCREASED SAFETY TERMINAL BLOCKS WIRING CONNECTION HUBS METRIC OR IMPERIAL HEATER FLANGE ANSI B16 5...

Страница 5: ...TEMPERATURE SENSOR THERMOCOUPLE OR RTD ELEMENT SUPPORT KEEPER Figure 3 Round Box Stilted Electrical Ratings Voltages up to 690 Vac 1 or 3 PH Wattages Up To 4 000KW 50 OR 60Hz Ambient Temperature Rating 60 C to 80 C Markings IECEx Ex eb IIC Gb T1 to T6 ATEX II 2 G Ex eb IIC TI TO T6 Gb Mounting Orientation Horizontal or Vertical Immersion Heater Square or Rectangular Box IP64 Stilted INCREASED SAFE...

Страница 6: ...ousings must be used In outdoor locations moisture resistant housings are required It is recommended to use a drip loop to prevent moisture from entering the terminal box via the wire or cable 4 Protect terminals of heating elements from drippings condensation fumes spray or any other substance which could result in element contamination 5 When melting solids by direct immersion a surface vent sho...

Страница 7: ...required Check factory for recommendations 8 If the heater is installed in a pressurized system a safety relief valve must be used to prevent a hazardous pressure buildup 9 Horizontal element support bundles may be necessary with an immersed length over 1270 mm 50 Refer to the heater drawings for details 10 For flange heaters installed in a pressurized system proper bolting hardware must be used t...

Страница 8: ...the heater TT and TN Systems A residual current protection device with a trip setting not exceeding 100mA The residual current protection device shall disconnect power supply to the heater when residual current above the trip setting has been detected IT Systems An insulation monitoring device designed to trip when the insulation between any phase of the electrical power supply to ground is less t...

Страница 9: ...NOTES ...

Страница 10: ...NOTES ...

Страница 11: ...NOTES ...

Страница 12: ...y but not so as to limit the generality of the foregoing includes physical chemical or mechanical abuse accident improper installation of the product improper storage and handling of the product improper application or the misalignment of parts No warranty applies to paint finishes except for manufacturing defects apparent within 30 days from the date of installation The Company neither assumes no...

Отзывы: