background image

88

O

p

er

at

io

n

 / M

ai

n

ten

an

ce

D. 

OPERATION

RISK OF EXPLOSION 

Do not operate heater at 

voltages higher than the rating specified on the 

nameplate. Failure to do this will cause elevated 

temperatures.

CAUTION

WARNING

WARNING 

Prior to operation an insulation 

resistance check must be performed. Heater 

with values less than 500,000 ohms should 

follow a drying process. Please contact factory 

for details on procedure if heater is under 

500,000 ohms

WARNING

FIRE HAZARD 

Heater should be submersed 

in the fluid for proper operation and to avoid 

element overheating that could result in fire or 

damage of the heater.

1. 

Check that all connections are tight.

2.  If a thermostat is provided, verify that it is operating properly 

by cycling it and verifying cutout.

3.  Perform an IR test prior to energization and verify that levels 

are acceptable (500,000 ohms min).

4.  Energize the heater and check for signs of hotspots in the 

electrical connections or vessel.

5.  Retorque all bolted fitting connections and all electrical 

connections after 10 cycles.

6.  For heaters installed in a tank, maintain a minimum of 51mm 

(2’’) of liquid above the heated portion of the element or 
element failure may result. Heating elements should be kept 
above sediment deposits or it may overheat and shorted life 
expectancy.

14.  The heaters must be protected against abnormal earth 

fault and earth leakage current. Depending on the electrical 
power system, the following protection device must be 
installed with the heater:

TT and TN Systems:

A residual current protection device with a trip setting not 
exceeding 100mA. The residual current protection device 
shall disconnect power supply to the heater when residual 
current above the trip setting has been detected.

IT Systems:

An insulation monitoring device designed to trip when the 
insulation between any phase of the electrical power supply 
to ground is less than 50Ω/V.

WARNING

WARNING 

Low megohm on heating elements 

with epoxy or hermetic seals cannot be serviced 

in the field. Typical resistance values when 

sealed are 1000 MΩ or greater.

E. 

MAINTENANCE

WARNING

WARNING

 Disconnect all power before servicing 

the heater or heated equipment. Failure to do so 

could result in personal injury and/or property 

damage. All maintenance and installation should 

be done by qualified personnel in compliance 

with local codes.

1. 

Heaters stored for prolonged periods may absorb moisture. 
Using a 500V DC megger (insulation resistance tester) check 
the value of the insulation resistance to ground for each 
circuit. Initial readings of over 500,000 ohms to ground are 
normally acceptable. Should lower readings be observed, 
check factory for instructions.

2.  Periodically check electrical connections for tightness 

and check wire insulation for any damage and replace if 
necessary.

3.  Remove the immersion heater periodically to inspect for 

corrosion, sludge build-up and for scale removal. Do not 
continue to use a heater showing visible signs of damage.

WARNING

WARNING 

When operating the heaters in 

a closed system or vessel, system designers 

must ensure that proper controls are used 

to maintain the temperature and pressure at 

normal levels.

Содержание CX Series

Страница 1: ...t all times in conjunction with temperature controls to limit the liquid temperature below the maximum allowable process design temperature b Terminal box internal surface temperature control to limit the surface temperature of the terminal box c Heater flange surface temperature control to limit the surface temperature of the flange d Heating elements sheath temperature controls to limit to the m...

Страница 2: ...th the following specific conditions of use 1 The heater shall be installed with electrical safety devices as described in the Installation Operating and Maintenance manual and in accordance with local codes and standards 2 It is the user s responsibility to connect the installed temperature sensors to safety devices as defined in IEC 60079 0 that are fail safe and can only be reset manually The t...

Страница 3: ...3 3 TABLE OF CONTENTS A Diagrams 4 B Description 6 C Installation 7 D Operation 8 E Maintenance 8 ...

Страница 4: ... or Vertical Immersion Heater Round Box IP66 Stilted TERMINAL BOX TEMPERATURE SENSOR THERMOCOUPLE OR RTD TERMINAL BOX SENSOR THERMOCOUPLE OR RTD A DIAGRAMS TERMINAL BOX TEMPERATURE SENSOR THERMOCOUPLE OR RTD INCREASED SAFETY TERMINAL BOX ROUND RATED IP66 AVAILABLE IN PAINTED STEEL OR STAINLESS STEEL INCREASED SAFETY TERMINAL BLOCKS WIRING CONNECTION HUBS METRIC OR IMPERIAL HEATER FLANGE ANSI B16 5...

Страница 5: ...TEMPERATURE SENSOR THERMOCOUPLE OR RTD ELEMENT SUPPORT KEEPER Figure 3 Round Box Stilted Electrical Ratings Voltages up to 690 Vac 1 or 3 PH Wattages Up To 4 000KW 50 OR 60Hz Ambient Temperature Rating 60 C to 80 C Markings IECEx Ex eb IIC Gb T1 to T6 ATEX II 2 G Ex eb IIC TI TO T6 Gb Mounting Orientation Horizontal or Vertical Immersion Heater Square or Rectangular Box IP64 Stilted INCREASED SAFE...

Страница 6: ...ousings must be used In outdoor locations moisture resistant housings are required It is recommended to use a drip loop to prevent moisture from entering the terminal box via the wire or cable 4 Protect terminals of heating elements from drippings condensation fumes spray or any other substance which could result in element contamination 5 When melting solids by direct immersion a surface vent sho...

Страница 7: ...required Check factory for recommendations 8 If the heater is installed in a pressurized system a safety relief valve must be used to prevent a hazardous pressure buildup 9 Horizontal element support bundles may be necessary with an immersed length over 1270 mm 50 Refer to the heater drawings for details 10 For flange heaters installed in a pressurized system proper bolting hardware must be used t...

Страница 8: ...the heater TT and TN Systems A residual current protection device with a trip setting not exceeding 100mA The residual current protection device shall disconnect power supply to the heater when residual current above the trip setting has been detected IT Systems An insulation monitoring device designed to trip when the insulation between any phase of the electrical power supply to ground is less t...

Страница 9: ...NOTES ...

Страница 10: ...NOTES ...

Страница 11: ...NOTES ...

Страница 12: ...y but not so as to limit the generality of the foregoing includes physical chemical or mechanical abuse accident improper installation of the product improper storage and handling of the product improper application or the misalignment of parts No warranty applies to paint finishes except for manufacturing defects apparent within 30 days from the date of installation The Company neither assumes no...

Отзывы: