ACT-7 QUICK START GUIDE

QUICK START GUIDE

Troubleshooting

Only a competent electrician should attempt to rectify electrical supply problems

.

Only a competent refrigeration engineer should work on th e refrigeration system

.

Symptoms

Possible causes

Action required

No air fl ow from room unit, display 
off .

Problem with  th e power 
supply.

Turn on electricity and/or check mains supply fuse.

No air fl ow from room unit, display 
on and showing temperature.

Mode switch in standby 
position.

Change th e position of th e mode switch to fan only 
or A/C.

No air fl ow from room unit, display 
on, defrost and A/C symbols 
showing.

ACT-7 is defrosting.

Machine in defrost mode, do not adjust anyth ing, 
machine will revert to normal operation aft er ten 
minutes.

Insuffi  cient air fl ow from room unit.

Blocked air fi lter.

Clean fi lter.

Insuffi  cient air fl ow from room unit. 
A/C indicator on, defrost symbol 
showing.

Temperature set too high.

Lower th e temperature and wait six minutes for time 
delay on start-up to elapse.

Insuffi  cient air fl ow from room unit.

Fan speed dial set to minimum.

Change th e position of th e fan speed dial.

No cooling.

HP alarm showing. High 
pressure trip.

No water or kinked hoses.

Insuffi  cient water.

External heat exchanger unit 
mounted in very high ambient 
temperature?

Water frozen? 

Reset alarm as described in resetting alarms section 
on page 8.

Top up th e ACT-7 room unit header tank with  water/
glycol mixture.

Add glycol (33%) as shown on page 5.

No cooling.

Flashing bucket full symbol.

Condensate pump not 
reducing water level.

Check th e lines for kinks and remove th em. Check th e 
room unit for leaks. Check to see if th e condensate 
tube is frozen.

No cooling.

LP alarm showing. Low 
pressure trip.

Loss of refrigerant.

Blocked fi lter.

Reset alarm as described in resetting alarms section 
on page 8.

Check th e fi lter and clean if necessary as shown on 
page 13.

HP/LP faults.

Recurring high pressure and low pressure faults may 
indicate th at th ere is an underlying problem th at needs 
investigating. Contact th e supplier of th e ACT-7 to 
arrange for servicing.

Содержание ACT-7

Страница 1: ...ACT 7 Quick start guide...

Страница 2: ...ot operate this device if it has missing damaged insecure guards or electrical components Ensure the device is sited on rm level ground Locate away from any possible unauthorised interference Ensure e...

Страница 3: ...operate from a standard domestic wall socket The size of any extension cable that may be used is 2 5mm2 minimum up to a maximum length of 10 metres For longer lengths 4 0mm2 cable must be used If the...

Страница 4: ...ng down the length of the room If there is more than one ACT 7 in the same area then they would normally be positioned side by side and equally spaced along the long wall all pointing in the same dire...

Страница 5: ...ct level when delivered Look through the inspection window and check that the level is between the MAX and MIN on the tank in the back of the room unit If necessary top up the room unit with antifreez...

Страница 6: ...ust be set to ducted mode Only use fan speeds in the RED range on the fan speed indicator for ducted operation Mode switch Top position fan only mode is selected In fan only mode air circulates but th...

Страница 7: ...ed temperature Press and hold the enter key for two seconds then release to enter the Settings menu With the Temperature option highlighted press the enter key Use the up and down keys to change the h...

Страница 8: ...w pressure faults are indicated by a ashing red H or L respectively and must be reset to resume normal operation See troubleshooting section Resetting the alarms Fault symbols In the Settings menu scr...

Страница 9: ...s full a blue bucket ashes on the console While this is ashing the ACT 7 continues to work for a further 30 seconds After 30 seconds if the condensate tank has not emptied the pump continues to operat...

Страница 10: ...Reset alarm Advanced settings Changing the o set An o set is used to calibrate the temperature shown on the main screen In the Settings menu scroll down to Advanced settings and push enter Highlight O...

Страница 11: ...11 ACT 7 QUICK START GUIDE Press enter to move onto the next digit When enter is pressed on the nal digit the value is stored...

Страница 12: ...Setting the language Advanced menu Enable Pin Language In the Advanced menu scroll down to Language and push enter Language Menu English Francais Deutsch Use the up and down arrows to select the desi...

Страница 13: ...ined in the system which may spill when the ACT 7 is moved Routine maintenance The air lter must be kept clean Never allow the lter to become obstructed with dust or dirt If allowed to do so poor perf...

Страница 14: ...erature and wait six minutes for time delay on start up to elapse Insufficient air ow from room unit Fan speed dial set to minimum Change the position of the fan speed dial No cooling HP alarm showing...

Страница 15: ...15 ACT 7 QUICK START GUIDE...

Страница 16: ...Calorex Heat Pumps Limited The Causeway Maldon Essex CM9 4XD United Kingdom t 44 0 1621 857171 e service calorex com www calorex com...

Отзывы: