Page 26
4.0 DATA SHEET
AA300AVH(F)
For accurate application sizing consult CALOREX Heat Pumps Ltd
Boiler not required for AA versions without LPHW.
MODE B = recovered heat biased to pool hall air
R407c Global warming potential (GWP) 1700.
1 mm WG = 9.8pa
1 mhd = 1.4psi
1 L/min = 0.22 gall/min
MODEL:-
Units
AA300
MINIMUM
ºC
15
MAXIMUM
ºC
36
DEHUMIDIFICATION
DUTY
VIA HEAT PUMP (30ºC/60% rh)
litres/hr
3.6
VIA HEAT PUMP (MODE B):-
kW
4.4
VIA LPHW @ 80ºC :-
kW
7.3
TOTAL :- (MODE B)
kW
9.8
RECOMMENDED BOILER CAPACITY
kW
7.3
RECOMMENDED BOILER CAPACITY
Btu's/hr
25000
FLOW RATE
l/min
10
Pressure Drop @ Rated Flow
m/hd
2.9
Max system w orking pressure
bar
6
V/ph/Hz 230V/ ~1N/50Hz
ELECTRICAL
TOTAL POWER CONSUMED (nominal) :- 'F' & NON 'F'
kW
2
MIN' SUPPLY CAPACITY (Max F.L.A.)
Amps
13
MAX' SUPPLY FUSE 1 ph N:- 'F' & NON 'F'
Amps
20
AIR FLOW (anemometer @ air on filter, w et evaporator)
m³/hr
1300 ±10%
MAX EXTERNAL STATIC PRESSURE:- NON 'F'
Pa
95
MAX EXTERNAL STATIC PRESSURE:- 'F'
Pa
110
DESIGN CONDITION Amps:-
1 ph N :- NON 'F'
Amps
1.04
1 ph N :- 'F'
Amps
1.5
FLA:- 1 ph N:-
Amps
2.6
NOMINAL POWER CONSUMED:-
kW
1.9
LRA:- 1 ph N:-
Amps
46
RLA:- 1 ph N:-
Amps
8.6
SOFT START Amps 1 ph N:-
Amps
24
Hermetic System
GAS CHARGE (R407c)
kg
2.6
LPHW battery volume
litres
1.15
IP RATING
IP
22
WIDTH (Unpacked)
mm
730
DEPTH (Unpacked)
mm
1025
HEIGHT (Unpacked)
mm
850
WEIGHT approx' (AA un-packed no options):-
kg
111
NOISE LEVEL @ 1m
dBA
61
GENERAL DATA
COMPRESSOR
MAIN FAN
PHYSICAL
DIMENSIONS
HEAT TO AIR
RECOMMENDED
BOILER CAPACITY
(AA+LPHW)
AIR TEMPERATURE
LIMITS