Page 33
DISPLAY
ERROR
ACTION
E1 OR -E1
PROBE INTERRUPTED OR
SHORT CIRCUIT
VERIFY CORRECT CONNECTION BETWEEN
PROBE AND STAT, THEN VERIFY CORRECT
FUNCTIONING OF PROBE.
EEPr
INTERNAL MEMORY ERROR
CHECK AND, IF NECESSARY REPROGRAMME
THE PARAMETERS FUNCTION
THERMOSTAT CONTROL
PARAMETER SETTING INSTRUCTIONS AA300AVH(F) HUMIDITY
The digital display may show the following codes, these are errors. Check the table below.
PARAMETER
FUNCTION
SETTING
NAME
GROUP
כ
SP (RELATIVE TO SET POINT )
nSP
FACTORY SETTING
1
SP1
SET POINT 1
60
SPLL
LOW SET POINT
15
SPHL
HIGH SET POINT
80
GROUP
כ
InP (RELATIVE TO THE MEASURED OUTPUT )
SEnS
PROBE TYPE
0.10
****
SSC
LOW SCALE LIMIT
0
****
FSC
HIGH SCALE LIMIT
100
dP
NO OF DECIMAL FIGURES
0
****
Unit
TEMP UNITS
FiL
INPUT DIGITAL FILTER
OFF
Fild
FACTORY SET PASSWORD
OFF
OFSt
MEASURING OFFSET
0
rot
ROT OF MEASURING STRAIGHT LINE
1.000
InE
OPE FUNC IN CASE OF ERROR
Our
OPE
OUTPUT PWR IN CASE OF ERROR
0
GROUP
כ
Out (RELATIVE TO OUTPUTS)
01F
FUNCTIONING OF OP1
1.rEG
02F
FUNCTIONING OF OP2
Alno
GROUP
כ
AL1 (RELATIVE TO ALARM AL1)
0AL1
OUTPUT, ALARM AL1 ADDRESSED
Out2
AL1t
ALARM AL1 TYPE
HidE
PARAMETER
FUNCTION
SETTING
NAME
GROUP
כ
AL1 (RELATIVE TO ALARM AL1) cont
Ab1
ALARM AL1 FUNCTIONING
0
AL1
ALARM AL1 THRESHOLD
5
AL1L
LOW THRESHOLD BAND ALARM AL1
-1999
AL1H
HIGH THRESHOLD BAND ALARM AL1
9999
HAL1
ALARM AL1 HYSTERESIS
3
AL1d
ACTIVATION DELAY OF ALARM AL1
OFF
AL1i
ALARM AL1 WHEN MEAS ERROR
no
GROUP
כ
LBA (RELATIVE TO LOOP BREAK ALARM )
OLbA
ALARM TYPE/SECOND OUTPUT
OFF
LbAt
HEAT/COOL CONTROL OUTPUT 1
OFF
GROUP
כ
rEG (RELATIVE TO CONTROL )
Cont
CONTROL TYPE
On.FA
Func
FUNCT. MODE OUTPUT 1rEg
CooL
HSEt
HYSTERESIS OF ON/OFF CONTROL
3
Slor
GRADIENT OF RAMP RISE
1nF
dur.t
DURATION TIME
1nF
SLoF
GRADIENT OF RAMP FALL
1nF
GROUP
כ
PAn (RELATIVE TO USER INTERFACE)
USRB
FUNCTION OF KEY 'U'
noF
diSP
VAR VISUALISED ON DISPLAY
dEF
AdE
SHIFT INDEXING FUNCTION
OFF
Edit
FST PROG ACTIVE SET POINT & ALARMS
SAE
SETTING INSTRUCTIONS (
THERMOSTATS MARKED TLK38)
NOTE : These parameter settings are programmed by the supplier to the figures shown below and
should not need altering.
1. To Program the Set Point. Press down P: SP (Set Point) and current set point value will be displayed alternately.
Press the or key to change the value of SP. Once the desired value is displayed press P to memorise the
value. The display will revert to the present reading.
NOTE : If anything else shows on the display leave alone for 1 minute, until the display returns to normal.
2. To Program the Parameters. Press and hold down the P key for approximately 2 seconds. You will then enter the
Programme Control Menu. Press the key to reach ConF then press P again and enter the Password -281 by
holding the key. If you pass -281 press the key to go back, then press P again, this will take you into the
Programmable Menu. To read or change the setting press P, then to change the setting
(if needed) press the or key . Once the correct setting is reached press P again. To move to the next setting
press the or key and repeat above.
*** Note some functions are not present either because they are instrument dependent or because they are disabled.
To return to Programmable Group Menu leave keys alone for approximately 20 seconds.
To return to Normal Mode leave alone for approximately 20 seconds.
123
123
123
123
123
123
123
123
123
123
123
123
123
123
123
123
123
123
123
123
123
123
123
123
123