15
Slave operator activation
Figure18
1.
Set SLAVE switch on SLAVE CONTROL BOARD to ON position.
2.
Use UL proved electric wire connect DATA- and DATA- from Master control board to
Slave control Board, then connect DATA+ and DATA+ accordingly.
3.
M/LINK light turn to solid bright.
Use Reversing Device
Figure 19
1. CLOSE ERD: when closing gate, increase/decrease amount of force by turning knob
Clockwise/counter clockwise.
2. OPENERD:When opening gate, increase/decrease amount of force by turning knob
Clockwise/counter clockwise.
3. Test device sensitivity every 6 months.