background image

27

USER 

8.2 - AUTOMATIC operation 

1.  Press button   until the heating clock 

corona will be displayed.

2. Icon    or    will light up to show 

which is the current set temperature 

level. 

If the thermostat function is disabled, 

pressing button 

 until the heating clock 

corona will be displayed enables the time 

programming of space heating set on 

the device (for any external thermostat 

connected to the heat interface unit). 

Содержание SATK Series

Страница 1: ...INSTRUCTION MANUAL SATKF2000 SATK S SERIES HIUS USER INTERFACE INSTRUCTION MANUAL SATKF2000 SATK S SERIES HIUs REMOTE CONTROL DEVICE...

Страница 2: ...I NL FR Other languages I FR NL Other languages...

Страница 3: ......

Страница 4: ...tion 0 1 C Room anti frost start temperature range 0 1 10 0 C Room anti frost end temperature start value 0 6 C Timer programmer resolution 30 minutes Maximum number of startings and shutdowns per day...

Страница 5: ...s Temperature display Select operating mode Set time and temperature Weekly program Change displayed value turn Select automatic manual press Confirm press Alarm reset Select temperature level day nig...

Страница 6: ...restore required Fault requiring technical service Day level Night level Service required LCD symbols Set day temperature Set night temperature Set heating temperature Set DHW temperature Set heating...

Страница 7: ...g up room DAY temperature 18 7 3 Setting up room NIGHT temperature 19 7 4 Setting up HEATING flow temperature 20 7 5 Setting up DOMESTIC HOT WATER temperature 21 7 6 Enabling disabling DOMESTIC HOT WA...

Страница 8: ...lts 35 11 2 Not restorable faults 36 12 Display values 37 12 1 Display set room temperature 38 12 2 Display temperature from domestic hot water probe 38 12 3 Display temperature from heating flow prob...

Страница 9: ...each of which having its own addressee Installer section this gives instructions regarding the accurate installation and configuration of the remote control device User section this gives detailed in...

Страница 10: ...r the use it has been designed for any different use is improper In case of repair contact only technical service centers authorized by the manufacturer Non compliance with the above may endanger the...

Страница 11: ...supply to operate and constitute also the communication between the two devices After installing it is immediately ready to run with its memorized standard program This program can be changed accordin...

Страница 12: ...ble raceway to connect it In case this is impossible any interference due to electric wires may cause poor working of the remote control device When used as a room thermostat install the SATK S remote...

Страница 13: ...f the device from the back of its fixing template 3 Insert both ends of the connecting wire into their proper seat on the fixing template Use the proper holes to install the SATK S remote control devi...

Страница 14: ...LER N B The connection is not polarized 4 Connect the cable to the terminal box 5 Fix your remote control device to its template First insert the upper partand then press and turn until its completely...

Страница 15: ...the installation is completed If it was done correctly the remote control device is now powered and the LCD display will show the following mes sage for a few seconds As soon as the connection is est...

Страница 16: ...onfigures the remote control device to be compatible with its installation position 1 Move the remote control device to OFF by repeatedly pressing button 2 Press the keys and and keep them pressed unt...

Страница 17: ...ge this value The corresponding parameter value will start blinking 3 Turn button to change the displayed value 4 If within 30 sec no key is pressed normal operation will be restored and the last chan...

Страница 18: ...quest for provision of space heating is accepted If set in MANUAL mode see 8 1 space heating is pos sible all day according to the signals from external thermostats The digits in the central part of t...

Страница 19: ...on temperature OFF It is the value to be added to the room setpoint in order to define the end of the space heating demand Example Tset point 20 0 C P03 0 5 C Tset point P03 20 0 0 5 20 5 C The centra...

Страница 20: ...6 Selecting operating mode Select the operating mode by pressing key several times The operating modes you can set are SELECTED STATUS OFF SUMMER WINTER HEATING ONLY ID ICONS 1 OFF all requests are d...

Страница 21: ...13 USER 2 SUMMER the heat interface unit is enabled to produce domestic hot water only 3 WINTER the heat interface unit is enabled to produce both domestic hot water and space heathing...

Страница 22: ...14 USER 4 HEATING ONLY the only operating mode enabled is space heating No matter which function has been selected the room anti freze function is always operative cfr respective section...

Страница 23: ...TEMPERTURE NIGHT HEATING FLOW TEMPERATURE ID ICONS SELECTED STATUS DOMESTIC HOT WATER TEMPERATURE COMFORT MODE HEATING MAX RETURN DHW MAX RETURN KD OUTSIDE PROBE ID ICONS These parameters may not be a...

Страница 24: ...ER 7 1 Setting up clock 1 Press key the hour will blink 2 Turn button to set the required value 3 Press button to confirm the in put value The hour will stop blink ing and the minutes will start blink...

Страница 25: ...et the value 5 Press button to confirm value The minutes stop blinking and the day of the week will start blinking Turn button to set the value Press button to confirm value The day of the week stops...

Страница 26: ...18 USER 7 2 Setting up room DAY temperature if thermostat enabled 1 Press key until icon starts blinking 2 Turn button to set the value you want...

Страница 27: ...19 USER 7 3 Setting up room NIGHT temperature if thermostat enabled 1 Press key until icon starts blinking 2 Turn button to set the temperature you want...

Страница 28: ...rature If the remote control device has been configured as modulating this parameter determines the max temperature value as computed by the modulation algorithms 1 Press key until icon starts blinkin...

Страница 29: ...21 USER 7 5 Setting up DOMESTIC HOT WATER temperature 1 Press key until icon starts blinking 2 Turn button to set the value you want...

Страница 30: ...bling disabling DOMESTIC HOT WATER pre heating 1 Press key until icon starts blinking 2 Turn button to enable ON disable OFF or enable according to the weekly domestic hot water pre heating program PR...

Страница 31: ...erface unit MAX is the set heating flow temperature This setting option is available only if the outside probe is connected and the use for modulation is enabled This parameter allows to select the st...

Страница 32: ...24 USER 7 8 Return temperature limits if the relative function is enabled The set points identified by icons and should not be changed These values should be set by technical personnel only...

Страница 33: ...pera ture set point is determined by the cor respondence between time day and the set weekly program In AUTOMATIC holiday mode the room temperature set point is determined by the correspondence betwee...

Страница 34: ...want 3 After 30 secs the central display will go back to showing the current ambient temperature 4 The set temperature can be changed again at any moment by turning button 5 The set temperature can be...

Страница 35: ...or will light up to show which is the current set temperature level If the thermostat function is disabled pressing button until the heating clock corona will be displayed enables the time programmin...

Страница 36: ...tton until HOL will be shown in the central display 2 Icon or will light up to show which is the currently set temperature level If the thermostat function is disabled pressing button until the heatin...

Страница 37: ...endent levels DAY and NIGHT the weekly heating program distributes these levels over the day Inside the remote control device there is a standard program to control the room temperature that can be ch...

Страница 38: ...cons and 1 will appear on the display and show the first day of the week Icons and the jumper are ON or OFF matching the DAY NIGHT level of the displayed time 2 Turn button in order to scroll the time...

Страница 39: ...button to confirm the day you selected and to move to the time The day of the week will stop blinking and the time will start blinking 5 Turn button to select the time 6 Press key to change the tempe...

Страница 40: ...to enable or disable the pre heating function by time ranges Inside the remote control device there is a standard program to control the DHW pre heating function the user can display and change it Th...

Страница 41: ...first day of the week 2 Press key Icon will light upon the display and show the pre heating program Icon pre heating enabled or pre heating tank disabled and the jumper are ON or OFF matching the leve...

Страница 42: ...program change zone icon and the day of the week will blink 4 Turn button to select the day you want 5 Press button to confirm the day you selected and to move to the time The day of the week will st...

Страница 43: ...learn about the type of fault refer to the heat interface unit instruction booklet There can be two kinds of faults those which can be restored by the user and those which cannot be restored 11 1 Res...

Страница 44: ...36 USER 11 2 Not restorable faults These faults are identified by the icon these faults cannot be reset by the user but require technical service...

Страница 45: ...e to display the following quantity values SELECTED QUANTITY SET ROOM TEMPERATURE DOMESTIC HOT WATER TEMPERATURE HEATING FLOW TEMPERATURE OUTSIDE TEMPERATURE RETURN TEMPERATURE ID ICON The value is di...

Страница 46: ...rmostat is enabled This is the temperature set for the activated temperature level DAY NIGHT MANUAL 12 2 Display temperature from domestic hot water probe This is the temperature read by the domestic...

Страница 47: ...heating flow probe This is the temperature read by the heating flow probe fitted in the heat interface unit 12 4 Display temperature from outside probe This is the temperature read by the outside prob...

Страница 48: ...40 USER 12 5 Display temperature from re turn probe This shows the primary return temperature 12 6 Display flow meter rotation frequency This is the rotation speed of the turbine of the flow meter...

Страница 49: ...The restored values are as follows Temperature DAY 20 C Temperature NIGHT 16 C Temperature MANUAL 20 C NIGHT 00 00 06 00 08 00 16 30 22 00 00 00 00 00 07 00 23 00 00 00 Weekly DHW pre heating program...

Страница 50: ...42 USER 1 Move the remote control device to OFF position 2 Press keys and and keep them pressed for longer than 5 secs 3 The operation is confirmed when dEF appears on the display...

Страница 51: ...en enabled Auxiliary contact closed This function has no effect on the provision of the heating services of the heat interface unit The lighting up of icons can therefore be ignored if the heat interf...

Страница 52: ...the operating modes the central heating demand is generated whenever the measured room temperature is lower then the activation threshold parameter P02 This grants protection of the heating installati...

Страница 53: ...a function In case the antilegionella function is enabled from 3 00 a m to 3 30 a m the domestic hot water temperature set point is increased to provide thermal disinfection of the heat exchanger Duri...

Страница 54: ...46 USER...

Страница 55: ...47 USER...

Страница 56: ...1 Caleffi S p A S R 229 n 25 28010 Fontaneto d Agogna NO Italia Tel 39 0322 8491 Fax 39 0322 863305 info caleffi com www caleffi com Copyright 2018 Caleffi...