Type of alarm
Program
Indication by alarm LE D
Indication by LE D dis play
Dis play on LC D
R ecording in log
AL1: flow probe
faulty
0 1A 1B 2
Generic alarm LED comes
On and Status OK LED goes
Off.
Alarm shown on LED display.
(“HI, “LO”, “SH”, “OP”
depending on case).
“Flow probe fault” alarm
displayed on LC D.
YES (AL1) Stored in the day
log.
R eturn probe fault
0 1A
The alarm LED remains Off
and the “Status OK” LED
remains On.
Remains Off if program 0,
and “HI, “LO”, “SH”, “OP”
displayed (depending on
case) if program is 1A.
NONE
Fault is recorded in the day
log.
AL2: return probe
fault
1B 2
Generic alarm LED comes
On and Status OK LED goes
Off.
Alarm shown on LED display.
(“HI, “LO”, “SH”, “OP”
depending on case).
“Return probe fault” alarm on
LC D (screen alternates with
working screen).
YES (AL2) Stored in the day
log.
Dis infection not
completed
0
The alarm LED remains Off
and the “Status OK” LED
remains On.
NONE
NONE
NONE
AL3: dis infection
not completed
1A 1B 2
“Generic alarm” LED comes
On and “Status OK” LED
goes Off.
NONE
“Disinfection incomplete”
alarm on LC D (screen
alternates with the working
screen).
YES (AL3) Stored in the day
log.
AL4: thermal
s hock in progres s
0 1A 1B 2
Generic alarm comes On
(but, if no other faults, the
Status OK LED also remains
On).
NONE
“Thermal shock in progress”
alarm on the LC D display.
YES (AL4) Stored in the day
log.
AL5: blackout
(mains power
failure)
0 1A 1B 2
The indicator LEDs remain
Off. Only the generic alarm
flashes.
Temperature indicators and
clock remain Off.
Temperatures are not
acquired.
LC D remains Off.
Recording of log data is
suspended.
YES (AL5) When power is
restored it is stored in the log.
AL6: appliance
res et
0 1A 1B 2
Generic alarm LED comes
On and “OK status” LED Off.
Time display 00 : 00 blinking.
Time on the LC D.
Entering screen displayed
Date and just set
Displaying of 01/01/2005 in
the LC D date field.
YES (AL6) Stored in the day
log.
AL7: battery
damaged
0 1A 1B 2
“OK status” LED goes Off.
“BTR FAIL” LED comes On.
(The generic alarm LED is
not lit).
NONE
“Battery damaged” appears
on LC D display (alternating
with the working screen).
YES (AL7) Stored in the day
log.
Operability after alarm (page 1)
25