ºF
ºC
Ω
ºF
ºC
Ω
ºF
ºC
Ω
ºF
ºC
Ω
-5
-20
100254
60
15
15310
130
54
3049
200
93
829
5
-15
72937
70
21
11882
140
60
2489
210
99
702
15
-10
53669
80
27
9297
150
65
2044
220
104
598
25
-4
39919
90
32
7333
160
71
1688
230
110
511
32
0
32648
100
38
5827
170
77
1402
240
115
439
40
4
26100
110
43
4664
180
82
1171
250
121
378
50
10
19900
120
49
3758
190
88
983
Temperature sensor resistance values
Location of cable connectors
B attery disconnec
B attery connected
ock disabled
factory setting)
B attery c onnec tion
hoc k
on
B attery
1
3
4
5
6
7
9
8
2
When making the electrical
connections, follow this sequence
for wiring the terminal strip and
tightening the seals:
1. Power supply
2. Mixing valve control
3. Mixed outlet temperature sensor
4. Return temperature sensor
5. RS485
6. Relay 3
7. Relay 1
8. Relay 4
9. Relay 2
Strain relief cord connectors (white)
are provided for all 9 controller
housing holes. Clear plastic plugs
also provided for unused holes.
Enabling functions-
Dipswitch settings
-Thermal Shock enable/disable.
-Internal battery (do this during
installation)
PIN
disable
Reset
Appliance fuse
400 mA - 250 V delayed
Mixing valve fuse
1 A - 250 V delayed
Rela
y
co
ntact
s
Electri
c
suppl
y
24
V
Mixin
g
val
ve
Battery connected
Battery disconnected
Battery connection
Thermal shock
activation
Shock
enabled
Shock
disabled
(factory setting)
Temperatu
re
sensors
Mixed outlet
Return
Common
Relay 1
Relay 2
Relay 3
Relay 4
Closes
Common
Opens
Earth
Earth
Neutral
Live
PIN code
disabling button
Reset button
Screw to close
the front cover
with hole
for lead-sealing
RS485
Interface
terminal
Microswitch
for enabling
thermal shock
function
Temperature
sensor terminal
Battery
To remove the electrical wiring base, turn it round and extract it from its housing.
–
+
ATTENTION: If the battery is not activated the battery alarm will be displayed.
CAUTION!
The controller is configured to automatically execute a daily rotation cycle to ensure ef
-
ficient ball operation and cleaning. This occurs directly after the disinfection program, if
active, or after 24 hours have elapsed if disinfection is not active. Deactive this function
through the ANTI-CLOG setting by entering the release code 5566 and confirming with ON-
OFF. Eliminating this function increases the risk of deposits forming on moving parts of
valve. If it is necessary to eliminate the disinfection function as well, proceed as follows:
1. disable the ANTI-CLOG function; 2. eliminate the disinfection function.
10