background image

Entering programs and settings

Controller operation is based on an internal clock with calendar and automatic time adjustment.
By navigating through the appropriate menu items and using the buttons on the front panel (“MENU”. 
“UP” 

, “DOWN” 

, and “OK”), the user can configure the controller, set the various parameters, 

and display the temperature log.

Functions of the configuration buttons

Description

Display

Button function

Effect

Menu item - arrows beside 
the row

“UP”

 

“DOWN” 

Moves the cursor to another 

row

+OK

Opens the related submenue

Menu

Go back to previous level

Other rows available
-arrows in the screen margin

“UP”

 

“DOWN” 

Displays other rows in the 

menu

Parameter selection
-cursor flashing

“UP”

 

“DOWN” 

Increases or descreases the 

parameter value

+OK

Confirms the setting - cursor 

disappears and the value 

becomes actual

Menu

Return to previous level 

without making changes

Whatever status the controller is in (except Low Power), navigation around the various menus to read 
the various settings and view the stored log data is always possible. However, for safety purposes, 

the 

settings data can be modified only when the controller is in “Adjustment” mode.

 In particular, 

parameters can not be modified while the controller is in “disinfection”, “flux” or “thermal shock” mode, 
and when the controller is in the “inactive with alarm” status. The various options are made availalble, 
depending on whether the return water temperature sensor has been enabled. To set programs 1B or 
2, the return water temperature sensor must be set as Present. To be able to remove the return water 
temperature sensor (i.e. set it as Present of Absent), program 0 or 1A must be set first.

Remote control

The controller can be controlled from a remote computer with the RS485 serial output connection, which 
can be accessed by hard-wired terminals and through the connector on the front panel. Since the interface 
is the multipoint bus type it is necessary for each controller connected on the bus to be identified by 
an appropriate address to avoid identification conflicts. For a detailed description of the operations and 
controls that are available from a remote location using this interface, refer to the relevant documentation.

Contact Caleffi for list of registers (points) for mapping LEGIOMIX information to ModBus. Configuation, 
mapping, hardware (routers, modem, etc.), and software are customer/user responsibility. Code NA10520 
Modbus-to-BACnet gateway is available separately for translating ModBus to BACnet.

19

Содержание LEGIOMIX 600094A

Страница 1: ...ams for circuit thermal disinfection to kill Legionella The controller is configurable via keypad or local or remote computer Depending on the type of system and habits of the user temperature levels...

Страница 2: ...the electronic mixing valve Be sure water hardness is less than 10 grains SAFETY INSTRUCTION CAUTION All work must be preformed by qualified personnel trained in the proper application installation a...

Страница 3: ...u sup rieure 100 F 38 C peut tre dangereux Au cours de l installation mise en service et l entretien de le r ducteur de pression le LEGIOMIX mitigeur lectronique prendre les precautions n cessaires af...

Страница 4: ...10 55 C Electric supply cable length 31 0 8 m Max distance for control signal wire 500 ft 150 m cable 2 conductor x AWG 18 800 ft 250 m cable 2 conductor x AWG 16 4 WARNING This product can expose yo...

Страница 5: ...C Ambient temperature range 32 120 F 0 50 C Protection class IP 54 wall mounting Class II appliance Mounting bracket DIN rail Mixing valve actuator current draw 1 A max 24 V Alarm relay rating R2 5 A...

Страница 6: ...nchors Mixing valve Actuator Mixed outlet water temperature sensor Return water temperature strap on sensor Spare fuses Installation and commissioning manual 115 24 VAC transformer 6 1 5 3 2 6 4 C 0 2...

Страница 7: ...bution control This measured temperature is used to check and control the temperature reached over all or part of the distribution network with this sensor placed at the end of the recirculation pipin...

Страница 8: ...ATURE STRAP ON SENSOR RS485 ModBus is integral to the controller It may be used directly and requires mapping by the user to access the data OR Optional gateway converts ModBus data to BACnet data ava...

Страница 9: ...erface terminal Microswitch for enabling thermal shock function Temperature sensor terminal Battery To remove the electrical wiring base turn it round and extract it from its housing Connecting temper...

Страница 10: ...les Enabling functions Dipswitch settings Thermal Shock enable disable Internal battery do this during installation Appliance fuse 400 mA 250 V Mixing valve fuse 1 A 250 V delayed Battery connected Ba...

Страница 11: ...2 x AWG 18 8 25 210 4 2 x AWG 18 8 25 210 5 3 x AWG 18 8 25 210 6 2 x AWG 16 6 25 160 7 2 x AWG 16 6 25 160 8 2 x AWG 16 7 180 9 2 x AWG 16 6 25 160 Connection cable cross sections and lengths for ci...

Страница 12: ...ator ON Status OK Battery Alarm 5 LED display Treturn return water recirculation temperature C only 6 Mixing valve open close LED 7 Thermal shock button 8 Navigation buttons Menu OK UP DOWN 9 RS 485 f...

Страница 13: ...LED red LED steadily ON when voltage is present Mixing valve LED red LED on when opening hot water blue LED on when opening cold water Controller OK status LED green LED steady ON when there are no fa...

Страница 14: ...ature of the mixed water at the valve outlet with temperature sensor and adjusts modulates the mixing valve position to maintain the desired set temperature Disinfection LEGIOMIX runs the disinfection...

Страница 15: ...the Shock function can be used if it is open it is not available see Back Panel section At the end of the Thermal shock phase the controller reverts to the adjustment modulating mode Low power LEGIOMI...

Страница 16: ...lackout or clock failure Relay 3 Second thermostat Wire in parallel to High Temperature thermostat Use to increase hot water supply temperature for thermal disinfection Relay 4 flushing valves Summary...

Страница 17: ...corded in the log The first time a button is pressed the relay opens again The other alarm indications are cleared at the next successful disinfection Program 1B This program can only be set if the re...

Страница 18: ...monitor only YES YES YES Adjustment temperature Flow SET1 68 185 F Flow SET1 68 185 F Flow SET1 68 185 F Flow SET1 68 185 F Disinfection temperature Flow SET2 104 185 F Flow SET2 104 185 F Recirculati...

Страница 19: ...mode In particular parameters can not be modified while the controller is in disinfection flux or thermal shock mode and when the controller is in the inactive with alarm status The various options a...

Страница 20: ...emperature during disinfection phase for programs 1B or 2 104 185 F 40 85 C 135 F Return sensor present Rec probe The return sensor is analog NTC NO absent YES present YES PGM program To modify the wo...

Страница 21: ...ue to gap in mechanical components during actuator movement until the internal valve ball starts to move in the opposite direction from 0 to 255 sec in 1 sec steps 005 sec tMOTOR Time required for the...

Страница 22: ...AL5 AL6 AL7 if they were activated on the day in question 24 hourly average values of the mixed outlet water temperature 24 hourly average values of the return water temperature If no disinfection wa...

Страница 23: ...even if there is a power failure While in operation the battery level of charge is checked periodically about avery 24 h ours and the recharge function is activated if neeeded When the battery rechar...

Страница 24: ...om 1 to 255 s econds UP DOWN OK tMOT OR 100 8 to 320 s econds UP DOWN OK ANT IC LOG ON ON OFF see instruct page14 UP DOWN OK T H E R MA L S H OC K T H E R MA L S H OC K S E T S H UP DOWN OK tS H 005 f...

Страница 25: ...On and Status OK LED goes Off NONE Disinfection incomplete alarm on LCD screen alternates with the working screen YES AL3 Stored in the day log AL4 thermal shock in progress 0 1A 1B 2 Generic alarm c...

Страница 26: ...ll actuations are inhibited the relays cannot be operated and therefore all the adjustment disinfection and thermal shock programs In this status the appliance goes into Low Power mode in order to ens...

Страница 27: ...254 min x x 20 0014 TIME flux after ending the disinfection 0 2550 sec x x 21 0015 TIME shock time of duration shock 1 4320 min x x 22 0016 SET REG mixing regulation set temperature 20 85 C x x 23 00...

Страница 28: ...UST b4 Internatiol System of Unit b5 LED display enable 34 0022 Forced activities 0 Shock activation x 1 Pin code reset 2 Disinfection reset 3 Alarm reset 4 Historical data reset 35 0023 TIME motor fr...

Страница 29: ...is installed within the hot water supply a Precaution should be taken to prevent the buildup of high temperature water in piping during periods of low or no use b Check valves should be provided to pr...

Страница 30: ...uses modified and information shown on the LED display LCD display and LEDs on the front panel 30 Maintenance During service regularly monitor the performance of the LEGIOMIX electronic mixing valve s...

Страница 31: ...e Temperature gauge B preventer Pump Expansion vessel Thermostat Safety relief valve Strainer Clock T T1 T2 T2 C 0 20 80 60 40 C 0 20 80 60 40 Application diagrams Recirculation not connected to tank...

Страница 32: ...ses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in...

Отзывы: