8
1)
Remove the insulation from the manifold.
2)
Undo the four nuts and take out the closure plate and the seal.
3)
Extract the modules from the threaded bars.
4)
Undo the drain and the closure cap.
Left-side version installation
The standard right-side version of the manifold can be installed in
the left-side version by proceeding as follows:
5)
Turn the end fitting with
steel rods upside down
180°.
6)
Rotate the end fitting 180°
lengthwise so that the front
connection is positioned as
shown
in
the
following
figure.
NOTE:
With a higher number of outlets it may be necessary to
repeat the tightening sequence several times.
To mount the manifold on the brackets follow the instructions under
“Mounting brackets – manifold”.
7)
Install the drain fully into the lower connection and the pocket
for the temperature gauge into the front connection.
8)
Reassemble the manifold by alternately inserting a seal and a
module, using the studs as a reference: the studs on each
module should be aligned with the end cap.
9)
After having inserted the same number of modules to match the
number of outlets, assemble the manifold with seal, closure
plate with grooves facing the inside, and the tightening nuts.
10)
To tighten the nuts, follow
the
adjustment
diagram
shown
opposite
with
the
following procedure:
- tighten with torque wrench
to 5 N·m.
- retighten with torque wrench
to 5 N·m.