background image

Technical specifications

Flanged connections

Materials

 

- body: 

    epoxy resin coated steel

 

- air vent body: 

 .   

            brass

 

- air vent hydraulic seal: 

                                 Viton

 

- air vent float: 

 .             Stainless steel 

 

- internal baffle: 

   304 series stainless steel

 

- shut off and drain valve body: 

                                 brass

 

Performance

Suitable fluids:                                                 water and non-hazardous glycol solution up to 50%
Max. operating pressure: 

                  150 psi (10 bar)

Working temperature range: 

with insulation 32–220°F (0–105°C) 

without insulation (vessel) 32–270°F (0–132°C)

Connections

Main connections: 

2"-14"ANSI B16.5 150 CLASS RF

Thermowell tap connection (8-14" only):                                                                      

      

 

- front center: 

 .                  ¾" NPT female

 

- inlet/outlet flanges:                                                                           ½" NPT female

Drain valve:                                                                                                 2 - 6": 1¼" NPT female

  

       

8 - 14": 2" NPT female

3

Содержание 548 Series

Страница 1: ...steel with flanged connections vent drain and insulation connections 2 2 1 2 3 4 ANSI NA548 series Hydraulic separator in steel with flanged connections vent drain and insulation ASME and CRN connecti...

Страница 2: ...nection size 1 inch 9 size 1 inch 9 size 1 inch 11 size 2 inch 12 Drain valve garden hose thread CAUTION If the hydraulic separator is not installed commissioned and maintained properly according to t...

Страница 3: ...lve body brass Performance Suitable fluids water and non hazardous glycol solution up to 50 Max operating pressure 150 psi 10 bar Working temperature range with insulation 32 220 F 0 105 C without ins...

Страница 4: ...efficient of resistance to the diffusion of vapor 1 300 Temperature range 32 210 F 0 100 C Fire resistance DIN 4102 class B2 Technical specifications of insulation flanged versions to 4 Internal part...

Страница 5: ...t Milwaukee Road Milwaukee WI 53208 T 414 238 2360 F 414 238 2366 18 Service Instructions There is no service required for the hydraulic separator CAUTION Corrosion or leakage can cause damage or inju...

Страница 6: ...red flow rate of either the primary circuit or the secondary circuit Union Flanged Size 1 1 11 2 2 2 21 2 3 4 5 6 8 10 12 14 gpm 11 18 26 37 60 80 124 247 300 484 792 1330 1850 2500 l s 0 7 1 1 1 6 2...

Страница 7: ...eparators NA10778 fits 1 and 1 union 548 series NA10796 fits 1 union 548 series NA10797 fits 2 union 548 series Replacement drain valve for 548 series union connection Hydro separators 538402 FD NPT x...

Страница 8: ...eriodically inspect for signs of corrosion or leakage If corrosion or leakage is noted the vent must be replaced Failure to follow these instructions could result in property damage and or personal in...

Отзывы: