N.B.: 

When installing the RH% limit sensor according to the

diagrams, as indicated, possible formation of condensation on the
surface. 

In areas where the max RH% limit sensor is installed,

adequate ventilation must always be present.

11)

SE

Outside sensor wiring. Connect the outside sensor using
2-core cable (2x0,75) to the connector provided on the unit.

12) 

SR

Return sensor wiring. Factory fitted.

13)

TA1

Room thermostat wiring. Optional.

14)

Pump shut-down variant. Sometimes the temperature
regulating unit is installed in a system where there may be

one or more users with different usage requirements. In this case, 
for users requiring ON/OFF operation, it may be necessary to 
shut down the unit circulator.
The electrical diagram shown below illustrates this possibility; 
the user auxiliary contact must be inserted in series with the
normal wiring.

15)

SM

Flow sensor wiring. Factory fitted.

16)

C

Summer - winter circuit changeover valve wiring.

F

This connection enables the 3-way valve to be activated

automatically for hydraulic deviation between the boiler circuit
and the chiller circuit. This takes place after the outside
temperature has risen above the value set at point 10 for at least
half an hour.
Ten minutes later, the regulating unit pump is activated.

17) 

KA

Chiller activation wiring. This activation takes place in the
same way as in point 16.

18)

Remote data transmission connector.

Table of sensor resistance values*

*

excluding max RH% limit sensor

Safety

If the flow or outside sensor shows an ohm resistance value outside
its working range (damaged or disconnected sensor), the following
operating state is automatically activated:
Pump OFF, Mixing valve OFF, LED 7 continuously lit.

Safety thermostat code 622001

Additional for use with underfloor heating systems.

- Range of adjustment:

5 ÷ 55°C

- Factory setting:

50°C

- Protection class:

IP 40

- Contacts load:

(C-1)  10(2,5)A / 250V

- Contacts load: 

(C-2)      1(1)A / 250V

PS

MA
MC

Brown

RH side

ter

minal strip

Pump shut-down wiring

Unit 152 pump

User auxiliary contact

6

7

8

Pump shut-down variant

°C

Ohm

-15 11.382
-12

9.912

-10

8.933

-6

7.439

-3

6.492

-2

6.206

0

5.632

°C

Ohm

0

5.632

2

5.187

4

4.742

6

4.347

8

4.000

10

3.553

15

2.971

°C

Ohm

20

2.431

25

2.000

30

1.655

35

1.376

40

1.150

45

966

50

815

°C

Ohm

55

690

60

587

65

501

70

430

75

370

80

319

85

276

°C

Ohm

90

240

95

209

100

183

SE
SE

LH side

ter

m

inal strip

Outside sensor

Connecting

wiring

Connector

C

1
2

+

°

C

KA

RH side

ter

minal strip

KA

C

F

M

N

Boiler circuit open

Chiller circuit open

12

3

6

9

18

17

16

15

14

1

3

12

1

1

10

9

8

7

6

5

4

3

2

1

24

23

22

21

20

19

WATCH

CALEFFI

30

40

50

60

70

80

90

-25%

+25%

-50%

0

22

24

26

28

30

32

34

The maximum heat energy that the panel can produce in relation
with the climate values recorded, can be reached by controlling the
below outlined parameters.

- Minimum flow temperature on the characteristic curve, which can

be selected through the microswitch (point 4 on the back panel).

- Sensor (code 150050) controlled maximum RH% limit.
- Room temperature controlled through room thermostat (code 151000).
- Room temperature and relative humidity controlled through a

dedicated fan-coil).

Содержание 152 Series

Страница 1: ...88 03 GB Function The temperature regulating unit is designed to guarantee the correct contribution of heating energy required by the user by measuring the outside and room temperature values to regul...

Страница 2: ...25 60 code 152651 GRUNDFOS UPS 25 80 04 Differential by pass valve with graduated scale 05 Flow temperature sensor 06 Outside temperature sensor connected via terminal 07 Circuit flow and return therm...

Страница 3: ...personal control of the operation of the system If this value matches the setting on the main printed circuit board item 6 PCB the regulation complies with the calculation criteria given by the chara...

Страница 4: ...actory setting 18 C An outside temperature higher than the set value will cause the following state circulator OFF and mixing valve closed An outside temperature 4 C higher than the set value will cau...

Страница 5: ...the primary It can be used to shut down the pump of the primary circuit or the boiler 10 UR Relative humidity sensor wiring This sensor is used to detect the limiting value of relative humidity to pr...

Страница 6: ...imit sensor Safety If the flow or outside sensor shows an ohm resistance value outside its working range damaged or disconnected sensor the following operating state is automatically activated Pump OF...

Страница 7: ...rence between the actual room temperature measured by the thermostat and the set temperature produces an amplified effect in relation to that produced by a similar variation in the outside temperature...

Страница 8: ...ics power supply 230 V 50 Hz rating 10 VA cycle time 240 s torque 10 N m Pump UPS 25 80 By pass valve with regulating scale from 0 05 channel clock for daily weekly programming Flow temperature sensor...