EXAMPLE II:
Setting of set points for carbon monoxide concentration and carbon
dioxide concentration, the MAX and MIN values of the analogue
outputs and calibration of the sensor
The access code and the recalibration of the sensor are time limited. If the time limit
is exceeded the sensor returns to DEFAULT.
ENTR =MENU(+) and ESC(-) are pushed simultaneously.
1.
At the start of the setting the sensor is in DEFAULT.
2.
Push MENU(+) once to reach the error code. The display shows E + the error
code number. No error is shown as E000.
(Push ESC(-) to return to DEFAULT if requested
3.
Push MENU(+) once. The display shows the CO set point e.g.
35 ppm and the carbon dioxide set point e.g. 750ppm.
(Push ESC(-) to return to DEFAULT if requested.)
4.
Push ENTR(+-) once. The display shows EC and two digits. Enter the access
code to the service menu. If the default code is used do like this:
Push MENU(+) until the digits stop. The display shows EC55.
If the correct code is not entered before the time limit exceeds the sensor
returns
to
DEFAULT.
5.
Push ENTR(+-) once. The display shows SPCO to set the carbon monoxide
set point.
6.
Push ENTR(+-) once. The display shows the carbon monoxide set point e.g.
ex 35 ppm. Push MENU(+) to increase the set point value in steps of 1 ppm.
Push ESC(-) to decrease the set point value in steps of 1 ppm.
7.
Push ENTR(+-) once when the set point is set. The display shows SPCO.
Push ESC(-) to return to DEFAULT.
8.
Push MENU(+) once to reach the carbon dioxide set point.
The display shows SP C.
9.
Push ENTR(+-) once. The display shows the carbon dioxide set point e.g. 750
ppm. Push MENU(+) to increase the set point value in steps of 50 ppm.
Push ESC(-) to decrease the set point value in steps of 50 ppm.
10.
Push ENTR(+-) once when the set point is set. The display shows SP C.
Push ESC(-) to return to DEFAULT.