Dokument
IMA 190
HFE507
Rev
5
Sid
37 (44)
EXAMPLE I:
Setting of the MAX value of the analogue outputs
The access code is time limited. If the time limit is exceeded the sensor returns to
DEFAULT.
ENTR =MENU(+) and ESC(-) are pushed simultaneously.
1.
At the start of the setting the sensor is in DEFAULT.
2.
Push MENU(+) once to reach the error code. The display shows E + the error
code number. No error is shown as E000.
3.
Push MENU(+) once. The display shows the CO set point e.g. 35.
4.
Push ENTR(+-) once. The display shows EC and two digits. Enter the access
code to the service menu. If the default code is used do like this: Push
MENU(+) until the digits stop. The display shows EC55. If the correct code is
not entered before the time limit exceeds the sensor returns to DEFAULT.
5.
Push ENTR(+-) once. The display shows SPCO to set the CO set point.
6.
Push MENU(+) once to reach the carbon dioxide set point. The display shows
SP C.
7.
Push MENU(+) once to reach the setting of analogue outputs. The display
shows AOUt.
8.
Push ENTR(+-) to reach the output to be set. The display shows An and two
digits e.g. An 01. Step to the requested output by pushing MENU(+).
9.
Push ENTR(+-) to reach the setting of the MIN value. The display shows Set
L.
10.
Push MENU(+) to reach the setting of the MAX value. The display shows Set
H.
11.
Push ENTR(+-) to set the MAX value of the output. The display shows the
numerical value in % e.g. the standard setting100.0 % or previously set value.
Push MENU(+) to increase the MAX value. Push ESC(-) to decrease the MAX
value. Push ENTR(+-). The display shows Sure. Push ENTR(+-) to save the
setting and return to Set H. Push MENU(+) or ESC(-) to return to Set H
without saving the new setting. Push ESC(-) to return to the output to be set,
item 12.Push ESC(-) once again to return to the setting of analogue outputs
item 11.