Functional description

 

 

Standard configuration:

 Out(1) is carbon monoxide output, Out(2) is carbon dioxide 

output and Out(3) is relay output. Out(4) is error status OR Out(3) is open. 
 
Out(1) = measuring signal for carbon monoxide concentration  
Out(2) = measuring signal for carbon dioxide concentration 
Out(3) = ON/OFF of demand of air quality. The relay is open in alarm situations and 
at   power loss. NOTE! There is a 2 minutes delay after start-up. 
Out(4) = error status OR OUT3 open, carbon monoxide concentration > 35 ppm OR 
carbon dioxide concentration > 1500 ppm. There is a 2 minutes delay after start-up. 
 

 

The control signal of air quality

 

 

 

Terminal 

 

Standard 

configuration 

 

Standard settings  

 

Standard function 

 

 
 

 

Power (+) 
 
 
 
Power ground (-) 

24 VAC/DC+  (+-20%), 
3W 
 
 
24 VAC/DC-

2W without output load 
 

The same ground reference has to be 
used for the M-SENSE III
 unit and for 
the control system!

 

Out(1) 

0-10VDC 

0-100 ppm CO 

Measuring signal carbon monoxide 

Out(2) 

0-10VDC 

0-2000 ppm CO

2

 

Measuring signal carbon dioxide  

Unmarked  Signal Ground (-)   

Connected to 

 via PTC fuse 

Relay  

 
Closed 
 
 
Open 

 
 
<    30 ppm CO 
< 1400 ppm CO

 
>    35 ppm CO 
> 1500 ppm CO

 

Air control Delay 2 minutes after start. 
 
The green LED is lit  
 
 
The relay is open in alarm situations and 
at power loss. The red LED is lit and the 
green is not lit. 

Out(4) 
Open 
collector 

Open 
 
 
 
Closed 
 

No error detected AND 
normal gas 
concentrations 
 
Error detected OR high 
gas concentrations 

Error status Delay 2 minutes after start. 
 

 

The red LED is lit if an error OR high gas 
concentrations are detected. If an error is 
detected also the yellow LED is lit   

Default configuration of

 

M-SENSE III

~

+

Содержание SenseAir M-SENSE III

Страница 1: ...styrenhet med programmerbara utg ngar b de f r rel och linj rstyrning av t ex luftfl den Den har m tv rdespresentation display Enheten uppkopplas direkt mot marknadens vanliga spj llregulatorer varvt...

Страница 2: ...allation se sidan 4 1 V ggplatta 6 H l f r v ggplattans hakar 2 Kretskort monterat vid leverans 7 Lock med kn ppning 3 Temperatursensor f r intern kompensering skymd 8 L sskruv f r locket skymd 4 Fukt...

Страница 3: ...verka m tarens funktion och noggrannhet 3 Kabelanslutning Montera kabelgenomf rning i storlek PG9 F r att h lla t tt kan endast en kabel f ras in genom varje kabelf rskruvning 4 Skruva fast v ggplatt...

Страница 4: ...stad utg ng Se not 1 3 4 5 Out 1 Out 2 5 Analog utg ng 1 Analog utg ng2 Signaljord 0 10 VDC eller 0 20 mA 2 10 VDC eller 4 20 mA Samma som utg ng 1 Ansluten till via PTC s kring Enligt bygeln f r Out...

Страница 5: ...vid behov F st sedan kabelf rskruvningen i h let och t ta ordentligt F r att h lla t tt kan endast en kabel f ras in genom varje kabelf rskruvning Kretskortet b r skruvas loss fr n kapslingen under h...

Страница 6: ...A 190 HFE507 Rev 5 Sid 6 44 Kretskortet till M SENSE III DI1 Plintanslutningar och byglar p M SENSE III M rkare positioner r grundinst llningar Kontakten DigIn_1 kan anv ndas f r forcerad ventilation...

Страница 7: ...Dokument IMA 190 HFE507 Rev 5 Sid 7 44 Anslutning av UG M SENSE III via skruvplinten vid kanalmontering...

Страница 8: ...matning Systemjord 24 VAC DC 20 3W 24 VAC DC 2W med obelastad utg ng Samma jordreferens m ste anv ndas till b de M SENSE III och till signalmottagaren Out 1 0 10VDC 0 100 ppm CO M tning av kolmonoxid...

Страница 9: ...p nning Ansluts bygeln i l ge Str m s f r Out 1 m tomr det 0 4 20 mA Ansluts bygeln i l ge Sp nning s f r Out 1 m tomr det 0 2 10 VDC Out 2 Str m Sp nning Ansluts bygeln i l ge Str m s f r Out 2 m tom...

Страница 10: ...tet under locket Den gula lysdioden blinkar till f r varje godk nd tryckning Tryckknappen MENU anv nds f r att stegvis v lja funktion ESC anv nds f r att komma tillbaka till tidigare vald niv Kretskor...

Страница 11: ...ing p displayen I normall get v xlar displayen CO2 xxxx ppm och CO xxx ppm Efter sp nningss ttning terg r displayen till normall get nskar man en permanent ndring av normal m tv rdesvisning anv nds PC...

Страница 12: ...Felkoden nollst lls med Entr 2 CO och CO2 b rv rdena nej V xla mellan CO och CO2 b rv rde med MENU 3 ECxx ja Kod f r tilltr de till servicemenyn Kodens defaultv rde r 255 11111111 tta tryck p MENU Tr...

Страница 13: ...Flera tryckningar p ESC kan beh vas f r att terg till NORMALL GET Ett tryck p Entr MENU ESC kan ndra viktiga systemparametrar Del av underh llsmenyn f r inst llning av b rv rden Funktion Linje Displa...

Страница 14: ...kan kontrollm tas med en multimeter 6e1 Sure nej Justeringen sparas med Entr Tryck p ESC leder tillbaka utan att v rdet sparas 6c2 SetH nej Leder till justering av MAX v rdet 6d2 Det inst llda MAX v r...

Страница 15: ...re siffror t ex E000 3 Tryck p MENU en g ng P displayen visas b rv rdet f r temperatur t ex 20 0C 4 Tryck ENTR en g ng P displayen visas EC och tv siffror Sl in tilltr deskoden till servicemenyn Om f...

Страница 16: ...yn till fl desjusteringen och trycka p ESC s att utg ngen terg r till normal m tning Del av underh llsmenyn med kalibreringsfunktioner 7 CALb ja Bakgrundskalibrering av CO2 sensorn och CO sensorn med...

Страница 17: ...t komma tillbaka till NORMALL GET 4 Tryck ENTR en g ng P displayen visas EC och tv siffror Sl in tilltr deskoden till servicemenyn Om f rinst lld kod anv nds g r s h r H ll MENU intryckt tills siffror...

Страница 18: ...r tidigare inst llt v rde Tryck p MENU f r att ka MAX gr nsen Tryck p ESC f r att minska MAX gr nsen Tryck p ENTR P displayen visas Sure Tryck p ENTR f r att f r att spara inst llningen och komma till...

Страница 19: ...r na sl cks n r CO halten eller CO2 halten verskrider inst llt v rde I det fall att regulatorn r kopplad till en spj llmotor i ventilationssystemet kommer regulatorn att signalera f r ett kat luftfl d...

Страница 20: ...efter installationen Sj lvdiagnostik Systemet inneh ller en fullst ndig sj lvdiagnostik som utf rs automatiskt varje g ng sp nningen sl s p F r M SENSE III kontrolleras interna sp nningsregulatorer o...

Страница 21: ...r ffar samtidigt med det flesta andra fel Kan indikera kortslutning eller felaktiga m tgivare och ing ngar terg r automatiskt n r orsaken till felet f rsvunnit Prova m taren i frisk luft Kontrollera t...

Страница 22: ...nadsfritt erh llas fr n Calectro RS232 kabeln art kod A232 CABLE kan best llas fr n Calectro Kabeln skall anslutas till UART glidkontakt se bilden p kretskortet Om kontrollparametrar skall ndras eller...

Страница 23: ...controller with programmable outputs for both relay and linear control of e g mixed air dampers humidifier and fans The measured values are shown on the display The unit can alternatively be connecte...

Страница 24: ...l installation see page 4 1 Wall plate 6 Hole for wall plate hooks 2 PCB factuary mounted in box 7 Snap in lid 3 Temperature sensor for internal compensation 8 Lid locking screw 4 RH sensor for intern...

Страница 25: ...g or else gas might leak through 4 Screw the wall plate onto the wall The wall plate has holes for three screws Drill holes for 3 5mm screws and put dowel into them Dowels and screws 3 5 x 25mm are in...

Страница 26: ...See note 1 3 4 5 Out 1 Out 2 Analogue Output 1 Analogue Output 2 Signal Ground 0 10 VDC or 0 20 mA 2 10 VDC or 4 20 mA Same as Output 1 Connected to via PTC fuse According to positions of Out 1 jumper...

Страница 27: ...35 ppm OR CO2 1500 ppm 8 Out 4 Drift disturbing alarm or gas alarm 9 10 DI 1 Extra terminal Test function N O If more holes are needed the box has several drill markings for holes in two dimensions P...

Страница 28: ...t IMA 190 HFE507 Rev 5 Sid 28 44 The PCB of M SENSE III DI1 Terminals and jumpers on M SENSE III The darker positions are default settings The terminal DigIn_1 may be used for forced ventilation ESC M...

Страница 29: ...Dokument IMA 190 HFE507 Rev 5 Sid 29 44 Connection of the UG M SENSE III via screw terminal at duct mounting...

Страница 30: ...ngs Standard function Power Power ground 24 VAC DC 20 3W 24 VAC DC 2W without output load The same ground reference has to be used for the M SENSE III unit and for the control system Out 1 0 10VDC 0 1...

Страница 31: ...nseAir communication protocol Out 1 Current Voltage Connection in position Current provides 0 4 20mA output range for Out 1 Connection in position Voltage provides 0 2 10VDC output range for Out 1 Out...

Страница 32: ...The push button MENU is available for selection of display value or maintenance commands whereas ESC is available to escape back from a selected level The sensor with push buttons The push button MEN...

Страница 33: ...onoxide readings presentation The push button MENU is used to select the indicated value on the display to be the error code or the set points of temperature and CO2 After power up the display will al...

Страница 34: ...ror code is reset with Entr 2 Present CO and CO2 set points no Toggle between display of temperature and CO2 set point with MENU 3 ECxx yes Access code to the service menu The default value of the cod...

Страница 35: ...de The Entr push MENU ESC eventually leads to execution of functions which causes temporary or permanently change of any parameter that affects the system outputs Function Line Display Time limit Func...

Страница 36: ...with a multimeter 6e1 Sure no The adjustment is saved by pressing Entr Press ESC to return without saving 6c2 SetH no Leads to adjustment of the MAX value 6d2 The present MAX value in of FS no Increa...

Страница 37: ...play shows SPCO to set the CO set point 6 Push MENU once to reach the carbon dioxide set point The display shows SP C 7 Push MENU once to reach the setting of analogue outputs The display shows AOUt 8...

Страница 38: ...m CO2 The calibration must be confirmed by pressing Entr The CO2 sensor is calibrated to 400 ppm CO2 and the CO sensor to 0 ppm CO 7a Sure yes Confirm that a background calibration shall be done 8 CAL...

Страница 39: ...two digits Enter the access code to the service menu If the default code is used do like this Push MENU until the digits stop The display shows EC55 If the correct code is not entered before the time...

Страница 40: ...he MAX value Push ESC to decrease the MAX value Push ENTR The display shows Sure Push ENTR to save the setting and return to Set H Push MENU or ESC to return to Set H without saving the new setting Pu...

Страница 41: ...lso a registration of increased CO level The CO sensor reacts much slower several minutes The red LED is lit and the green LED is turned off when the CO or CO2 concentration goes above the pre set val...

Страница 42: ...SENSE III the internal voltage regulators and outputs are checked In addition constantly during operation the sensor probes are checked against failure by checking the valid dynamic measurement range...

Страница 43: ...of error disappearance Try sensor in fresh air Check connections of temperature and relative humidity probe Check detailed status of measurements with UIP software version 4 3 and higher See Note 1 6...

Страница 44: ...f charge The RS232 cable article code A232 CABLE is needed and can be ordered from Calectro The cable is to be connected to the UART port slide connector For change of control parameters and re calibr...

Отзывы: