Electrical connections
The power supply
has to be connected
to
and
.
is considered as
system ground.
The same ground reference has to be used for
the
M-SENSE III unit
and for any connected device!
Unless different transformers are used, special
precautions need to be taken.
PLEASE NOTE! The M-SENSE III signal and power supply
grounds are common.
PLEASE NOTE!
The same ground reference has to be used for
the M-SENSE III unit and for the control system!
#
Connection
Terminal
Function
Electrical Data
Remarks
1
2
Power (+)
Power ground (-)
24 VAC/DC+ (+-20%),
3W
24 VAC/DC-
2W without output load
See note 1!
3
4
5
Out(1)
Out(2)
Analogue Output 1 (+)
Analogue Output 2 (+)
Signal Ground (-)
0-10 VDC or 0-20 mA,
2-10 VDC or 4-20 mA,
Same as Output 1
Connected to
via
PTC fuse
According to positions of Out(1)
jumper and start point selection.
See note 2!
According to positions of Out(2)
jumper and start point selection.
See note 2!
See note 1!
6
7
6
7
Normally closed relay
Open at alarm
situations and power
loss
Contact free relay
minimum load 1mA/5V
rated load
0,5A/125VAC;
1A/24VDC
Triggered by register Out(3)
8
8
Analogue Output 4 (+)
or Open Collector
0-10 VDC
Max 0,5A, 55VDC /
40VAC
(half-wave rectifier
protection)
According to positions of
Out(4).
See note 2 & 3!
9
10
DigIn_1
Digital Input 1
Closed contact current
1mA
Open contact voltage
max 5V
Do not apply any voltage on
this input!
Electrical terminal connections for
M-SENSE III
~
+
~
+