User’s Guide — 45
Finding Voltage Drop Wire Size
A 20-amp single-phase 208-volt load will
be located 175 feet away from the
source. Assuming a 3% allowable volt-
age drop, what is the size of 75°C con-
ductor re-quired for this branch circuit?
Steps
Keystrokes
Display
Reset calculator
[On/C]
0.
Set to 75°C
[Set] [7]
3Ø 75 Cu 0.
Set to 1-phase
[Set] [1]
1 PH
Enter amps
20 [Amps]
20. AMPS
Enter volts
208 [Volts]
208. VOLT
Enter distance
175 [Length]
175. FEET
Enter allow. VD%
3 [VD%]
3.0 DROP V %
Find wire size
[WireSz]
8 CU
AWG VD WIRE SIZE
Find actual
voltage drop
[VD%]
5.4 DROP V
Find % v.drop
[VD%]
2.6 DROP V %