EVERSKY
™
MS-CDF-019
–
Manufacturing Nr: 22
0001→
Version B
Update: 2022/06/14
24/70
IX.8.b.
E3-DSP-CLD
As standard, the unit comes with a local mobile wired HMI with a 10m length cable and housed in the control compartment. This
HMI is directly connected to the “Ext. Disp.” port of the controller. This cable can be extended within a limit of 100m
.
IX.8.c.
ED-Touch
Refer to the ED-Touch manual for the operation and the connection to the controller.
IX.9.
Firefighter remote stop control (ADP)
Replace the factory shunt between terminals (21) and (22) by a NC (Normally
Closed) dry contact acting as firefighter remote control.
At the opening of the contact, the 24Vac supply is cut off depriving the
control of the unit of any function (no more display available).
The isolation motorized dampers on the fresh air side and the on the exhaust
air side close by means of their automatic return spring.
All the actuators return to their resting position.
X.
DRAINAGE OF CONDENSATE
X.1.
Gravity evacuation
As standard, the unit is designed for a drainage of condensate by gravity (without high point). The installation of a siphon is to be
expected at the time of installation of the unit.
The position of the condensate evacuation and the kind of connection interface are presented in chapter I.4 External connections.
Provide a slope of 2 to 3 % in direction of condensate evacuation and ensure that the collector is neither under nor overpressured.
X.2.
Evacuation by condensate lift pump (optional)
X.2.a.
General information
If condensate drainage by gravity is not possible, a condensate lift pump with mounting accessories is available as an optional kit.
The condensate lift pump makes it possible to evacuate the condensate at a higher level from the unit (for example on the roof, in
another room
…)
or in case of high point on the evacuation line. The operation of the pump does not affect acoustic qualities of the
unit.
Non-compliance with the installation rules of the condensate siphon can lead to an overflow of the condensate
pan and an internal flooding of the unit that can cause damages to the equipment, damages, malfunctions, and
endanger the occupants and staff.
11
21
12
22
13
23
14
24
15
25
16
26
17
27
18
28
19
29
20
30
B2
ADP
Firefighter
remote control
Non-compliance with the installation rules of the condensate siphon can lead to an overflow of the condensate
pan and an internal flooding of the unit that can cause damages to the equipment, damages, malfunctions, and
endanger the occupants and staff.
Содержание EVERSKY 1100
Страница 43: ...EVERSKY MS CDF 019 Manufacturing Nr 220001 Version B Update 2022 06 14 43 70 Supply fan Extract fan...
Страница 48: ...EVERSKY MS CDF 019 Manufacturing Nr 220001 Version B Update 2022 06 14 48 70 XVII GENERAL WIRING DIAGRAM...
Страница 49: ...EVERSKY MS CDF 019 Manufacturing Nr 220001 Version B Update 2022 06 14 49 70...
Страница 69: ...EVERSKY MS CDF 019 Manufacturing Nr 220001 Version B Update 2022 06 14 69 70 NOTES Date Stakeholder Comments...
Страница 70: ...EVERSKY MS CDF 019 Manufacturing Nr 220001 Version B Update 2022 06 14 70 70 Date Stakeholder Comments...