EVERSKY
™
MS-CDF-019
–
Manufacturing Nr: 22
0001→
Version B
Update: 2022/06/14
19/70
Connect power supply wires directly on the main switch terminal (marker 1 and 3).
Connect the protective earth (PE) wire on the crimped nut near the main switch (provide a eyelet lug for M6 screw).
The protective earth wire must be slightly longer than the line and neutral wires.
Power supply connection to the main switch
Attach and clamp strongly the power supply cable to a
fixed part (frame, cable tray…).
IX.
ELECTRICAL CONNECTION OF EXTERNAL DEVICES
The EASY control embedded in the EVERSKY unit provides the user with specific inputs and outputs to know or force the operation,
or to possibly control remoted devices.
IX.1.
Alarm report output (DO5) - 24Vac to be relayed
Factory setting = NO (Normally Open) output
Output in idle state (open) = no active alarm or presence of Class
C alarm (warning).
Active output (closed) = Class A or B alarm is active.
See XX.7 List and meaning of alarms.
24Vac output to be relayed.
Содержание EVERSKY 1100
Страница 43: ...EVERSKY MS CDF 019 Manufacturing Nr 220001 Version B Update 2022 06 14 43 70 Supply fan Extract fan...
Страница 48: ...EVERSKY MS CDF 019 Manufacturing Nr 220001 Version B Update 2022 06 14 48 70 XVII GENERAL WIRING DIAGRAM...
Страница 49: ...EVERSKY MS CDF 019 Manufacturing Nr 220001 Version B Update 2022 06 14 49 70...
Страница 69: ...EVERSKY MS CDF 019 Manufacturing Nr 220001 Version B Update 2022 06 14 69 70 NOTES Date Stakeholder Comments...
Страница 70: ...EVERSKY MS CDF 019 Manufacturing Nr 220001 Version B Update 2022 06 14 70 70 Date Stakeholder Comments...