Mark
Components
B1
Terminal block for fans condensate lift pump
B2
Terminal block for safeties
B3
Terminal block for commons GDO
B4
Terminal block for commons AGND (30)
B5
Terminal block for commons
G (1) →
+24V
B6
Terminal block for cC (4)
B7
Terminal block for cC (4)
B8
Terminal block for commons
G (1) → +24V
B9
Terminal block for commons AGND (90)
INS1
…3
Crimped nuts for protective earth (PE) connection
K1
Electrical heating coil power switch
KD
Electrical pre-heating coil power switch
REG
Controller
TRAFO
Control transformer
VII.3.
Control terminal blocks and user connections
B1
B2
B3
B4
B5
B6
B7
B8
B9
Terminal blocks of electrical board
Designation
Definition
Terminals
Connection
ADP
Firefighter remote stop
21-22
To be connected to the terminals of a NC dry contact of the
firefighter remote stop.
(Shunt between terminals 21-22 at the factory)
THA
Frost protection thermal switch
23-27
To be connected to the NC dry contact of the THA frost
protection thermal switch (PREMIUM BC and INFINITE BC)
THS
Thermal safety switch
23-27
To be connected to the NC dry contact of the THS thermal
safety switch (PREMIUM BE and INFINITE BE)
THSD
Preheating coil thermal safety
switch
24-28
To be connected to the NC dry contact of the THSD thermal
safety switch (INFINITE BE and INFINITE BC)
MF PV
Reduced speed external running
DI3 Cont 73
To be connected to a NO external dry contact.
MF GV
Normal speed external running
DI4 Cont 74
To be connected to a NO external dry contact.
ARR EXT
External stop
DI5 Cont 75
To be connected to a NO external dry contact.
V3V BC
3-way valve for hot water
heating coil
AO1 Cont 76 + 78
To be connected to the 3WV of the hot water heating coil (see
XVIII WIRING DIAGRAM OF CUSTOMER CONNECTIONS)
AL
Alarm report
DO5 Cont 47
24Vac output available when operating fault
(Caution 24Vac output to be relayed)
7
5 6
3 4
1 2
11
21
12
22
13
23
14
24
15
25
16
26
17
27
18
28
19
29
20
30
31
46
34
49
32
33
47
48
38
53
35
50
36
51
37
52
39
54
55
56
57
40
41
42
58
59
60
43
44
45
73
74
75
63
64
65
62
71
72
61
76
77
66
67
69
70
78
79
80
68
Содержание EVERSKY 1100
Страница 43: ...EVERSKY MS CDF 019 Manufacturing Nr 220001 Version B Update 2022 06 14 43 70 Supply fan Extract fan...
Страница 48: ...EVERSKY MS CDF 019 Manufacturing Nr 220001 Version B Update 2022 06 14 48 70 XVII GENERAL WIRING DIAGRAM...
Страница 49: ...EVERSKY MS CDF 019 Manufacturing Nr 220001 Version B Update 2022 06 14 49 70...
Страница 69: ...EVERSKY MS CDF 019 Manufacturing Nr 220001 Version B Update 2022 06 14 69 70 NOTES Date Stakeholder Comments...
Страница 70: ...EVERSKY MS CDF 019 Manufacturing Nr 220001 Version B Update 2022 06 14 70 70 Date Stakeholder Comments...