COMMERCIAL IN CONFIDENCE
Page 6
1.5 Level 2 - parameters in address order
Parameter
Name
Size
Address
(hex)
R/W
ModBus
Function
read/write
Internal Storage, Step rate in
Internal units, Limits
Comments
SP1.P
SP1_ontime
SP1_proptime
2
2
0062
0078
R
R
3
3
not stored
must be computed as
SP1_ontime/SP1_proptime
*100%
Disp
bit
002A
RW
1/5
0=low res, 1= high res
Hand
1
018F
RW
3/6
No scaling
step by 1
min 0=off, max=100
PL.1
1
0190
RW
3/6
No scaling
step by 1
min=0, max=100
PL.2
1
0191
RW
3/6
No scaling
step by 1
min=0, max=100
SP2.A
1
0192
RW
3/6
0=none, 1=dvhi, 2=dvlo, 3=band,
4=fshi, 5=fslo, 6=cool
9500P
7=EOP
SP2.b
1
0193
RW
3/6
0=none, 1=ltch, 2=hold, 3=ltho,
4=nlin
Hi.SC
2
0094
RW
3/6
HiSc * 10
[LIN]
step by 0.1 or 1
min=Sensor Min, max=Sensor Max
Lo.SC
2
0096
RW
3/6
LoSc * 10
[LIN]
step by 0.1 or 1
min=Sensor Min, max=Sensor Max
Inpt
1
0198
RW
3/6
0=none, 1=Tcb, 2=Tce, 3=Tcj,
4=Tck, 5=Tcl, 6= Tcn, 7=TcR,
8=Tcs, 9=Tct, 10=RTD, 11=lin1
12=lin2, 13=lin3, 14=lin4, 15=lin5
9500
11=lin
12-15 unused
Unit
1
0199
RW
3/6
0=none, 1=C, 2=F, 3=bar, 4=PSI,
5=Ph, 6=Rh, 7=set