Generator
Unit
8 kW
10 kW
12 kW
14 kW
16 kW
17 kW
20 kW
Rated Max. Continuous
Power Capacity (Watts*)
7,000 NG
8,000 LP
9,000 NG
10,000 LP
12,000 NG
12,000 LP
13,000 NG
14,000 LP
16,000 NG
16,000 LP
16,000 NG
17,000 LP
18,000 NG
20,000 LP
Rated Voltage
120/240
Rated Voltage at No-Load
(NG)
220-235
247-249
Rated Max. Continuous Load
Current (Amps)
120 Volts** (NG/LP)
240 Volts (NG/LP)
58.3/66.6
29.2/33.3
75.0/83.3
37.5/41.6
100.0/100.0
50.0/50.0
108.3/116.6
54.2/58.3
133.3/133.3
66.6/66.6
133.3/141.6
66.6/70.8
150.0/166.6
75.0/83.3
Main Line Circuit Breaker
35 Amp
45 Amp
50 Amp
60 Amp
65 Amp
65 Amp
100 Amp
Circuits*** 50A, 240V
-
-
-
1
1
1
-
40A, 240V
-
-
1
1
1
1
-
30A, 240V
1
1
1
-
-
-
-
20A, 240V
-
1
-
1
1
1
-
20A, 120V
1
3
3
4
5
5
-
15A, 120V
5
3
5
4
5
5
-
Phase
1
Number of Rotor Poles
2
Rated AC Frequency
60 Hz
Power Factor
1
Battery Requirement
Group 26R, 12
Volts and 350 CCA
Minimum
Group 26R, 12 Volts and 525 CCA Minimum
Weight (unit only in lbs.)
340
387
439
439
455
455/421
450
Enclosure
Steel
Steel
Steel
Steel
Steel
Steel/Aluminum
Aluminum
Normal Operating Range
-20° F (-28.8° C) to 77° F (25° C)
* Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc.
Maximum power decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 6 C (10 F) above 16 C (60 F)
ambient temperature.
** Load current values shown for 120 volts are maximum TOTAL values for two separate circuits. The maximum current in each circuit must not exceed the value
stated for the 240 volts.
*** Circuits to be moved must be protected by same size breaker. For example, a 15 amp circuit in the main panel must be a 15 amp circuit in the transfer switch.
Stator WindinG reSiStance ValueS / rotor reSiStance
8 kW
10 kW
12 kW
14 kW
16 kW
17 kW
20 kW
Power Winding: Across 11 & 22
0.123-0.1439
0.090-0.105
0.100-0.116
0.100-0.116
0.074-0.086
0.074-0.086
0.0415-0.0483
Power Winding: Across 33 & 44
0.123-0.1439
0.090-0.105
0.100-0.116
0.100-0.116
0.074-0.086
0.074-0.086
0.0415-0.0483
Excitation Winding: Across 2 & 6
0.776-0.902
0.511-0.594
0.876-1.018
0.876-1.018
0.780-0.906
0.780-0.906
0.731-0.850
Rotor Resistance
3.01-3.49
3.22-3.74
7.96-9.25
7.96-9.25
8.79-10.21
8.79-10.21
10.02-11.65
sPEcificatioNs
0G9266revA.indd 4
10/15/2008 11:25:39 AM
Содержание FOR BYPASS AND FAN POWERED HUMIDIFIERS
Страница 56: ...Page 54 NOTES 0G9266revA indd 54 10 15 2008 11 27 21 AM...
Страница 189: ...Page 187 0G9266revA indd 187 10 15 2008 11 28 53 AM...
Страница 190: ...Page 188 0G9266revA indd 188 10 15 2008 11 28 53 AM...
Страница 191: ...0G9266revA indd 189 10 15 2008 11 28 53 AM...