background image

7

Condensate Drain Pipe Sizes

Refer to table 12 for the required sizes.

Table 12 – Drain Pipe Sizes

UNIT SIZE

OUTSIDE DIAMETER

18K---54K

1(25.4)

Refrigerant Charge

The outdoor units can be matched with multiple indoor units, and

thus a different amount of charge might be required when matched

with the 40MKCB**F or 40MKQB**F units. Charge to

Sub--cooling Delta from Rating Plate Value as stated below.

Table 13 – Charge Requirements

SYSTEM

TYPE

NOMINAL

CAPACITY

kBTU/Hr

OUTDOOR UNIT

INDOOR UNIT

CHARGE TO

SUB--COOLING

DELTA FROM

RATING PLATE

VALUE

Cooling

Only

18

24AHA418A003

124ANS018000

40MKCB18F--- ---3

12

24

24AHA424A003

124ANS024000

40MKCB34F--- ---3

12

30

24AHA430A003

124ANS030000

40MKCB34F--- ---3

12

34

24AHA436A003/5/6

124ANS036000

40MKCB34F--- ---3

8

48

24AHA448A003/5/6

124ANS048000

40MKCB54F--- ---3

12

54

24AHA460A003/5/6

124ANS060000

40MKCB54F--- ---3

10

Heat

Pump

30

25HHA430A003

224ANS030000

40MKQB36C--- ---3

11

36

25HHA436A003/5/6

224ANS036000

40MKQB36C--- ---3

14

48

25HHA448A003/5/6

224ANS048000

40MKQB48C--- ---3

11

NOTE

:

The above additional charge is required amount for

line lengths up to 25 ft. (7.6 m). For line lengths exceeding 25 ft.
(7.6 m), an additional charge is required. Refer to the

Residential Long Line Guide

.

Metering Device

The 40MKC(Q)*F unit uses a TXV. The outdoor unit uses a type

B accurator. The cooling metering device is installed with the

indoor unit, while the heating metering device is installed with the

outdoor unit. One metering device is required for the cooling only

system and two are required for the heat pump systems. Refer to

Table 14 for a breakdown of each unit’s metering devices.

Table 14 – Metering Devices

SYSTEM SIZE

kBTU/hr

COOLING ONLY

HEAT PUMPS

40MKCB**C

40MKQB**C

25HHA4/224ANS

18

TXV

-

-

24

TXV

-

-

30

TXV

TXV

0.055"

34

TXV

-

-

48

TXV

54

TXV

-

-

36

-

TXV

0.063"

48

TXV

TXV

0.073"

POWER AND CONNECTING CABLES --

FIELD SUPPLIED

Recommended Connection Method for Power and

Communication Wiring (To minimize

communication wiring interference)
Power Wiring:

The main power is supplied to both the indoor and the outdoor units.

The field supplied connecting cable consists of three (3) wires. Two

wires are high voltage AC power and one is a ground wire. Consult

your local building codes and the NEC (National Electrical Code) or

CEC (Canadian Electrical Code) for special requirements. All wires

must be sized per NEC or CEC and local codes. Use Electrical Data

table MCA (minimum circuit amps) and MOCP (maximum over

current protection) to correctly size the wires and the disconnect fuse

or breakers respectively. Per caution note, only copper conductors with

a minimum 300 volt rating and 2/64--inch thick insulation must be

used.

Communication Wiring:

A separate shielded Stranded copper conductor only, with a 600

volt rating and double insulated copper wire, must be used as the

communication wire from the outdoor unit to the indoor unit.

To minimize voltage drop of the communication wire, use the wire

size and maximum lengths shown in Table 15.

Table 15 – Maximum Wire Lengths

WIRE SIZE

LENGTH ft. (m)

18AWG

50 ft. (15 m)

16AWG

50 ft. (15 m) to 100 ft. (30 m)

13AWG

100 ft. (30 m) to 200 ft. (60 m)

EQUIPMENT DAMAGE HAZARD

Failure to follow the following caution may result in

equipment damage or improper operation.
Wires should be sized based on NEC and local codes.
Use copper conductors only with a 600 volt rating and double

insulated copper wire.

CAUTION

!

USER INTERFACE

The indoor unit is supplied with a wireless remote control to

operate the unit (an Owner’s Manual is supplied with the unit). The

following accessories are available.

S

Wall mounted control

OPERATING RANGE

Ensure that the system operates within the application guidelines

shown in the following tables.

Table 16 – Cooling Operating Range

Outdoor

Unit

MAXIMUM

MINIMUM

DB °F (°C)

WB °F (°C)

DB °F (°C)

WB °F (°C)

125 (51.7)

-

55 (12.8)

-

Indoor Unit

90 (32)

-

64 (18)

-

Table 17 – Heating Operating Range

Outdoor

Unit

MAXIMUM

MINIMUM

DB °F (°C)

WB °F (°C)

DB °F (°C)

WB °F (°C)

75 (23.9)

67 (19.4)

17 (-8.3)

-

Indoor Unit

80 (27)

32 (0)

-

ACCESSORIES

An extensive list of field installed accessories is available for both

indoor and outdoor units. Identify what accessories, if any, are

required for the application at hand and consult the separate

installation instructions for the accessories. Some of the

accessories, especially on the indoor units, can be installed much

easier if planned ahead.

Содержание 40MKCF

Страница 1: ...ce agency or your distributor or branch for information or assistance The qualified installer or agency must use factory authorized kits or accessories when modifying this product Refer to the individ...

Страница 2: ...3 124ANS018000 40MKCB18F 3 24 24AHA424A003 124ANS024000 40MKCB34F 3 30 24AHA430A003 124ANS030000 40MKCB34F 3 34 24AHA436A003 5 6 124ANS036000 40MKCB34F 3 48 24AHA448A003 5 6 124ANS048000 40MKCB54F 3 5...

Страница 3: ...S INDOOR Unit W D H Hook D W Bracket A0150266 Fig 6 440MKCB F 40MKQB F Unit and Bracket Dimensions Table 4 Dimensions Indoor INDOOR UNIT SIZE BTU Hr HEIGHT H in mm WIDTH W in mm DEPTH D in mm OPERATIN...

Страница 4: ...S OUTDOOR Fig 7 Outdoor Unit Dimensions NOTE S Center of Gravity S All dimensions are in inches unless noted Table 5 Dimensions Outdoor UNIT SIZE MINIMUM MOUNTING PAD DIMENSIONS 18 24 23 x 42 30 36 48...

Страница 5: ...5 Table 6 Dimensions ACs Table 7 Dimensions SI ACs Table 8 Dimensions HPs 2 224ANS030000 224ANS036000 224ANS048000 Table 9 Dimensions SI HPs 224ANS030000 224ANS036000 224ANS048000 Legend X Yes 0 No...

Страница 6: ...tion to prevent recirculation of discharge air SYSTEM REQUIREMENTS Clearances Allow sufficient space around the indoor and outdoor unit for proper airflow circulation and servicing Refer to Fig 8 and...

Страница 7: ...ting cable consists of three 3 wires Two wires are high voltage AC power and one is a ground wire Consult your local building codes and the NEC National Electrical Code or CEC Canadian Electrical Code...

Страница 8: ...nstall indoor units near a direct source of heat such as direct sunlight or a heating appliance S Do not install units too close to humid conditions S Where an optimum air distribution is ensured S Wh...

Страница 9: ...TXV kit Flexible piping is recommended CAUTION Failure to follow the following caution may result in equipment damage or improper operation Insulate liquid and vapor pipes connecting to indoor and out...

Страница 10: ...to each suspension bolts making space for hanging the indoor unit S Hang the indoor unit to the suspension bolts between two nuts see Fig 18 S Screw the nuts to suspend the unit S Adjust level of the...

Страница 11: ...adient of 2 without obstruction see Fig 20 DO NOT install the drainpipe to an upward position It may cause water to flow back to the unit S Make a trap of at least 2 in 51 mm in depth to prevent unple...

Страница 12: ...y damage the compressor at start up When more than 80 ft 24 4 m of interconnecting tubing is used consult the Residential Long Line Application Guide for required accessories 3 Insulate both lines A m...

Страница 13: ...njury or death Before performing service or maintenance be sure indoor unit main power switch is turned OFF and indoor blower has stopped Lock out and tag switch with a suitable warning label Power Wi...

Страница 14: ...the unit side panel and connect to the control terminal strip using either Fig 28 for AC units or Fig 29 for Heat Pump units A150280 Fig 28 40MKCB F 24AHA4 or 124ANS Connecting Diagram A150282 Fig 29...

Страница 15: ...9 30 48 3 117 21 8 1 45 28 8 50 36 5 208 230 3 253 197 71 9 3 1 2 12 8 20 48 5 83 1 13 7 1 45 18 6 30 36 6 460 3 506 414 38 5 6 0 6 7 6 15 48 6 41 6 2 0 8 8 6 15 Table 20 40MKCB F Electrical Data INDO...

Страница 16: ...re L1 Nullline L2 interface 24V interface CN 20 Network module interface CN 12 Vertical swing motor interface CN 13 horizontalswing motor interface CN 10 Display boardinterface CN 15 Compressor signal...

Страница 17: ...N2 3 Transformer CN25 Controls signal interface R C CN7 Sens or LivewireL1 NulllineL2 interface 24V interface CN20 Networkmodule interface CN12 Verticalswingmotor interface CN13 horizontalswingmotor i...

Страница 18: ...18 OUTDOOR UNIT SCHEMATIC DIAGRAM Fig 36 25HHA4 224ANS Wiring Diagram 208 230V 1 Phase Fig 37 25HHA4 224ANS Wiring Diagram 208 230V 3 phase...

Страница 19: ...19 Fig 38 225HHA4 224ANS Wiring Diagram 460V 3 phase...

Страница 20: ...nect switch to the unit s control box Use copper wire only between the disconnect switch and unit 5 If any accessories are being installed refer to the individual accessory instructions for guidance o...

Страница 21: ...ect manifold gage charge hose to a charge port of the low side service valve see Fig 43 2 Connect charge hose to vacuum pump 3 Fully open the low side of manifold gage see Fig 44 4 Start vacuum pump 5...

Страница 22: ...t mode the unit will run in cooling and heating on heat pumps regardless if there is demand or not TEST OPERATION FOR UNDER CEILING CONSOLE Perform test operation after completing gas leak and electri...

Страница 23: ...down Procedure The system may be pumped down in order to make repairs on the low side without losing complete refrigerant charge 1 Attach pressure gage to suction service valve gage port 2 Front seat...

Страница 24: ...s NO MALFUNCTION RUNNING LAMP TIMER LAMP DEFROSTING LAMP ALARM LAMP DISPLAY DIGITAL TUBE 1 Open or short circuit of T1 temperature sensor X X X E2 2 Open or short circuit of T2 temperature sensor X X...

Страница 25: ...w or too high Check temperature setting Outdoor unit fan faulty Replace outdoor fan Air or other non condensable gasses in the circuit Drain refrigerant evacuate and recharge CAUTION Do not vent refri...

Страница 26: ...0 W Morris St D Indianapolis IN 46231 Edition Date 10 15 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 40MKC Q B F...

Отзывы: