ELECTRICAL DATA
Table 18 – 24AHA4/124ANS Electrical Data
UNIT SIZE --- ---
voltage,series
V/PH
OPER VOLTS*
COMPR
FAN
MCA
MAX FUSE**
or
CKT BRK AMPS
MAX
MIN
LRA
RLA
FLA
18--- ---3
208/230/1
253
197
56.3
9
0.5
11.8
20
24--- ---3
62.9
10.9
0.5
14.1
25
30--- ---3
73
14.1
0.7
18.3
30
36--- ---3
77
14.1
1.2
18.8
30
48--- ---3
124
18.5
1.2
24.3
40
60--- ---3
152.5
23.7
1.45
31.1
50
36--- ---5
208/230/3
253
197
71
9
1.2
12.5
20
48--- ---5
83.1
13.7
1.2
18.3
30
60--- ---5
110.0
15.9
1.45
21.4
35
36--- ---6
460/3
506
414
38
5.6
0.6
7.6
15
48--- ---6
41
6.2
0.6
8.4
15
60--- ---6
52.0
7.1
0.80
9.7
15
Table 19 – 25HHA4/224ANS Electrical Data
UNIT SIZE --- ---
V/PH
OPER VOLTS*
COMPR
FAN
MCA
MAX FUSE**
or
voltage,series
MAX
MIN
LRA
RLA
FLA
CKT BRK AMPS
30--- ---3
208/230/1
253
197
64
12.8
1.2
17.2
30
36--- ---3
77
14.2
1.2
19
30
48--- ---3
117
21.8
1.45
28.8
50
36--- ---5
208/230/3
253
197
71
9.3
1.2
12.8
20
48--- ---5
83.1
13.7
1.45
18.6
30
36--- ---6
460/3
506
414
38
5.6
0.6
7.6
15
48--- ---6
41
6.2
0.8
8.6
15
Table 20 – 40MKCB**F Electrical Data
INDOOR UNIT
SIZE
BTU/Hr
V---Ph---Hz
VOLTAGE RANGE
FAN
POWER
Min (V)
Max (V)
FLA (A)
Min Ckt Amp (A) Max Fuse CB Amp
(A)
18K
208---230---1---60
187
253
0.71
1
15
24K --- 34K
208---230---1---60
187
253
0.7 x 2
3
15
48K---54K
208---230---1---60
187
253
0.95 x 2
3
15
Table 21 – 40MKQB**F Electrical Data
INDOOR UNIT SIZE
BTU/Hr
V---Ph---Hz
VOLTAGE RANGE
FAN
POWER
Min (V)
Max (V)
FLA (A)
Min Ckt Amp
(A)
Max Fuse CB
Amp (A)
30K--- 48K
208---230---1---60
187
253
0.95 x2
3
15
LEGEND
FLA
--- Full Load Amps
HACR---
Heating, Air Conditioning, Refrigeration
LRA---
Locked Rotor Amps
NEC---
National Electrical Code
RLA
--- Rated Load Amps (compressor)
*Permissible limits of the voltage range at which the unit will operate satisfactorily
**
Time---Delay fuse.
Complies with 2007 requirements of ASHRAE Standards 90.1