background image

12

PERSONAL INJURY AND/OR EQUIPMENT

DAMAGE HAZARD

Failure to follow this caution may result in personal injury

and/or equipment damage.

Be sure unit panels are securely in place prior to rigging.

CAUTION

!

1. Rig the unit. Keep the unit upright and lift using a sling.

Use cardboard or padding under the sling, and spreader bars

to prevent sling damage to the unit. See Fig. 23 for the
center of gravity reference.

2. Mount unit on a solid concrete pad or platform.
3. Isolate unit and piping from structure.
4. If a heat pump is being installed, use a field-- provided snow

stand or ice rack where prolonged subfreezing temperatures
or heavy snow occurs.

5. On cooling only units, an accessory stacking kit can be used

when units are to be stacked. See installation instructions
provided with accessory kit.

A07396

Fig. 23 – Lifting Unit with Sling

Mounting Unit on Wall

The units can also be mounted on the wall using the accessory

mounting kit.

COMPLETE OUTDOOR REFRIGERANT

CONNECTIONS

Follow the following general guidelines:

1. Use refrigerant grade field – supplied tubing. Refer to Table

11 for the correct line sizes.

2. Do not use less than 10 ft (93.05 m) of interconnecting

tubing.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
If any section of pipe is buried, there must be a 6 in. (152.4

mm) vertical rise to the valve connections on the outdoor

unit. If more than the recommended length is buried,

refrigerant may migrate to cooler, buried section during

extended periods of system shutdown. This causes

refrigerant slugging and could possibly damage the

compressor at start--up.

When more than 80 ft. (24.4 m) of interconnecting tubing is used,

consult the Residential Long Line Application Guide for required

accessories.

3. Insulate both lines. A minimum of 1/2 inch foam pipe

insulation is recommended.

4. Run the refrigerant tubes as directly as possible and avoid

unnecessary turns and bends.

5. Suspend refrigerant tubes to avoid damage to insulation or

tubes so they do not transmit vibration to the structure.

6. When passing refrigerant tubes through the wall, seal the

opening so rain and insects do not enter the structure. Leave
some slack in refrigerant tubes between structure and
outdoor unit to absorb vibration.

Connection at Outdoor Unit

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage

or improper operation.
To prevent damage to unit or service valves observe the

following:

S

A brazing shield

MUST

be used.

S

Wrap service valves with wet cloth or use a heat sink
material.

24AHA4/124ANS Units:

1. Assemble the connector tube to the factory supplied filter

drier by:

S

Braze the field supplied connector to the inlet of the filter

drier (see Fig. 24).

A09536

Fig. 24 – Cooling Only Connector Tube Assembly

2. Braze the completed filter drier assembly to the liquid

service valve.

3. Connect the field supplied line set to the filter drier

assembly and the suction valve. A sweat connection is
required at the suction valve and flare connection is required

for the mixed phase line.

4. Insulate any exposed areas between the line set and the

liquid valve.

25HHA4/224ANS Units

1. Assemble the connector tubes to the factory supplied filter

drier by brazing the factory supplied flare connectors to the

inlet and outlet for the filter drier (see Fig. 25).

A09537

Fig. 25 – Heat Pump Connector Tube Assembly

Содержание 40MKCF

Страница 1: ...ce agency or your distributor or branch for information or assistance The qualified installer or agency must use factory authorized kits or accessories when modifying this product Refer to the individ...

Страница 2: ...3 124ANS018000 40MKCB18F 3 24 24AHA424A003 124ANS024000 40MKCB34F 3 30 24AHA430A003 124ANS030000 40MKCB34F 3 34 24AHA436A003 5 6 124ANS036000 40MKCB34F 3 48 24AHA448A003 5 6 124ANS048000 40MKCB54F 3 5...

Страница 3: ...S INDOOR Unit W D H Hook D W Bracket A0150266 Fig 6 440MKCB F 40MKQB F Unit and Bracket Dimensions Table 4 Dimensions Indoor INDOOR UNIT SIZE BTU Hr HEIGHT H in mm WIDTH W in mm DEPTH D in mm OPERATIN...

Страница 4: ...S OUTDOOR Fig 7 Outdoor Unit Dimensions NOTE S Center of Gravity S All dimensions are in inches unless noted Table 5 Dimensions Outdoor UNIT SIZE MINIMUM MOUNTING PAD DIMENSIONS 18 24 23 x 42 30 36 48...

Страница 5: ...5 Table 6 Dimensions ACs Table 7 Dimensions SI ACs Table 8 Dimensions HPs 2 224ANS030000 224ANS036000 224ANS048000 Table 9 Dimensions SI HPs 224ANS030000 224ANS036000 224ANS048000 Legend X Yes 0 No...

Страница 6: ...tion to prevent recirculation of discharge air SYSTEM REQUIREMENTS Clearances Allow sufficient space around the indoor and outdoor unit for proper airflow circulation and servicing Refer to Fig 8 and...

Страница 7: ...ting cable consists of three 3 wires Two wires are high voltage AC power and one is a ground wire Consult your local building codes and the NEC National Electrical Code or CEC Canadian Electrical Code...

Страница 8: ...nstall indoor units near a direct source of heat such as direct sunlight or a heating appliance S Do not install units too close to humid conditions S Where an optimum air distribution is ensured S Wh...

Страница 9: ...TXV kit Flexible piping is recommended CAUTION Failure to follow the following caution may result in equipment damage or improper operation Insulate liquid and vapor pipes connecting to indoor and out...

Страница 10: ...to each suspension bolts making space for hanging the indoor unit S Hang the indoor unit to the suspension bolts between two nuts see Fig 18 S Screw the nuts to suspend the unit S Adjust level of the...

Страница 11: ...adient of 2 without obstruction see Fig 20 DO NOT install the drainpipe to an upward position It may cause water to flow back to the unit S Make a trap of at least 2 in 51 mm in depth to prevent unple...

Страница 12: ...y damage the compressor at start up When more than 80 ft 24 4 m of interconnecting tubing is used consult the Residential Long Line Application Guide for required accessories 3 Insulate both lines A m...

Страница 13: ...njury or death Before performing service or maintenance be sure indoor unit main power switch is turned OFF and indoor blower has stopped Lock out and tag switch with a suitable warning label Power Wi...

Страница 14: ...the unit side panel and connect to the control terminal strip using either Fig 28 for AC units or Fig 29 for Heat Pump units A150280 Fig 28 40MKCB F 24AHA4 or 124ANS Connecting Diagram A150282 Fig 29...

Страница 15: ...9 30 48 3 117 21 8 1 45 28 8 50 36 5 208 230 3 253 197 71 9 3 1 2 12 8 20 48 5 83 1 13 7 1 45 18 6 30 36 6 460 3 506 414 38 5 6 0 6 7 6 15 48 6 41 6 2 0 8 8 6 15 Table 20 40MKCB F Electrical Data INDO...

Страница 16: ...re L1 Nullline L2 interface 24V interface CN 20 Network module interface CN 12 Vertical swing motor interface CN 13 horizontalswing motor interface CN 10 Display boardinterface CN 15 Compressor signal...

Страница 17: ...N2 3 Transformer CN25 Controls signal interface R C CN7 Sens or LivewireL1 NulllineL2 interface 24V interface CN20 Networkmodule interface CN12 Verticalswingmotor interface CN13 horizontalswingmotor i...

Страница 18: ...18 OUTDOOR UNIT SCHEMATIC DIAGRAM Fig 36 25HHA4 224ANS Wiring Diagram 208 230V 1 Phase Fig 37 25HHA4 224ANS Wiring Diagram 208 230V 3 phase...

Страница 19: ...19 Fig 38 225HHA4 224ANS Wiring Diagram 460V 3 phase...

Страница 20: ...nect switch to the unit s control box Use copper wire only between the disconnect switch and unit 5 If any accessories are being installed refer to the individual accessory instructions for guidance o...

Страница 21: ...ect manifold gage charge hose to a charge port of the low side service valve see Fig 43 2 Connect charge hose to vacuum pump 3 Fully open the low side of manifold gage see Fig 44 4 Start vacuum pump 5...

Страница 22: ...t mode the unit will run in cooling and heating on heat pumps regardless if there is demand or not TEST OPERATION FOR UNDER CEILING CONSOLE Perform test operation after completing gas leak and electri...

Страница 23: ...down Procedure The system may be pumped down in order to make repairs on the low side without losing complete refrigerant charge 1 Attach pressure gage to suction service valve gage port 2 Front seat...

Страница 24: ...s NO MALFUNCTION RUNNING LAMP TIMER LAMP DEFROSTING LAMP ALARM LAMP DISPLAY DIGITAL TUBE 1 Open or short circuit of T1 temperature sensor X X X E2 2 Open or short circuit of T2 temperature sensor X X...

Страница 25: ...w or too high Check temperature setting Outdoor unit fan faulty Replace outdoor fan Air or other non condensable gasses in the circuit Drain refrigerant evacuate and recharge CAUTION Do not vent refri...

Страница 26: ...0 W Morris St D Indianapolis IN 46231 Edition Date 10 15 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 40MKC Q B F...

Отзывы: