The Chassis View
3-5
MMAC-Plus Management Views
EPIM
This color-coded Þeld displays the operating status of the Environmental
ModuleÕs Ethernet Port Interface Module (EPIM) interface: gray if not used, green
if operational, or red if malfunctioning.
LCD
This Þeld is not operational for this release of MMAC-Plus Remote Management.
Temperature
This Þeld displays the room temperature (in Fahrenheit) as measured by the
external ambient temperature sensor. This Þeld is also color-coded, as follows:
Humidity
This Þeld displays the non-condensing humidity level of the MMAC-Plus.
System Status
The System Status portion of the Chassis view is reserved for future functionality.
Table 3-1. Room Temperature Display
Temperature Range
Color Code
Temperature Condition
43¡ and below
Red
Cold
44-54¡ F
Yellow
Cool
55-90¡
Green
Normal
91-101¡ F
Yellow
Warm
102¡ F and above
Red
Hot
Table 3-2. Humidity Display
Humidity Level
Color Code
Humidity Condition
0-45%
Yellow
Static Risk (Dry)
46-94%
Green
Normal
95% and above
Red