EACIE Evacuation Alert Control and Indicating Equipment
Page 31 of 38
Approved Document No. DFU5030020 Rev 1
Installation and Programming Manual
7.6
Event Log Functions
This function lists, filters and resets the panel’s event or fault log.
At Access Level 3, press the
button and the window shown below appears:
The
Show Event Log
button, when pressed, lists both the
panel’s event and alarm log (up to 9999 events). This
includes faults and system events.
The
Show Fault Log
button, when pressed, lists the panel’s
fault log. Typically, faults include missing devices, earth
faults, open/short circuit faults and watchdog resets.
The
Clear Event Log
button, when pressed, clears the respective log from the panel’s memory. To ensure a
log is not erased by mistake, a five-digit security code requires entering using the touchscreen’s numeric
keypad. The default code is
32767
.
The window shown left is a typical list of saved events.
Press the
and
buttons (or use the scroll bar) to scroll
through the list. Events are listed in chronological order with
the most recent listed last. When the log is full, the oldest
record is deleted and replaced by the newest record.
To filter the log, press one of the blue event log buttons and
the window shown below appears.
The
Filters
button, when pressed, allows events to be listed
by Date Range or Device Address.
Event log button
(displays panel events)