8
12.
The unit operating as a Wiegand output reader
In this mode the unit supports a Wiegand 26 bit output so the Wiegand data lines can be connected to any
controller which supports Wiegand 26 bit input.
Alarm output time
To set the alarm output time (0-3
minutes). Factory default 1 minute
.
5
. .
0 – 3
. .
#
.
Keypad lockout & alarm output options
If there are 10 invalid cards or 10 incorrect PIN’s entered in a 10 minute period, either the keypad will lockout for 10 minutes
or both the alarm and inside buzzer will operate for 10 minutes, depending on the option selected below.
Normal status: No keypad lockout or
alarm (factory default)
.
7
. .
0
. .
#
.
(Factory default)
Keypad lockout
.
7
. .
1
. .
#
.
Alarm and inside buzzer operation
.
7
. .
2
. .
#
.
To turn off the alarm
To reset the door forced open alarm
.
Read valid card
.
or
.
Master code
. .
#
.
To reset the door open too long alarm
Close the door
or
.
Read valid card
.
or
.
Master code
. .
#
.