The format of these records are:
Name
Offset
Description
AGE
0
time in seconds when the wireless device
generated this data.
DATA_0,
DATA_1,
DATA_2,
DATA_3
1, 2, 3, 4
Data is generated by wireless device.
The format for this data can be found in the
Serial MODBUS Sensor Application Definition
document
Battery
5
register value / 100 = x.xx Volts
RSSI
6
a negative number from -20 to -110 dBm
The FRR is auto zeroed when no new data comes in.
Ref.6 - Wireless Device Registers
This section defines the location and function of all the remotely
located registers available for access through the MODBUS
interface. Every wireless device has been allotted 50 possible
registers. The table below enumerates the address allotment.
FCADDRESSFORMULA=42001+(50*SLOT)
Raw Address FORMULA=2000+(50*SLOT)
Example:
Register Name
Address
Register Name
Address
WDR [0]
FC 42001,
Raw 2000
WDR [49]
FC 44451,
Raw 4450
The following table represents the supported Wireless Device
Registers. They contain the pertinent data and configurations
populated from the remote device. Through these registers, a
user is capable of interpreting additional data, setting new
configurations, and sending other control-related messages
(CNTL) to the remote device. Unknown or unused values are
defaulted to 0x0000.