Page 19
No.1 battery address: 100000 No.2 battery address: 010000
Please refer to the configuration list in Appendex1.
Note: Make sure of the highest address of BMS connecting to the BMU when communicating with the inverter .
6 Cleaning and maintenance
6.1
Cleaning
The B-BOX system is recommended to be cleaned periodically. If the enclosure is in a dirty condition, please use a soft and dry brush or a
vacuum to remove the dirt.
Do not use liquids such as solvents, abrasives or corrosive liquids in the enclosures.
6.2
Maintenance
6.2.1 Recharge requirement with normal storage
The B-BOX should be installed in a position with a temperature range of -10
℃~
+50
℃
and where the humidity is less than 80%.The
load-bearing of the battery
’
s packaging is less than 300Kg, so stacking more than 7 modules is not recommended..
When the battery stored for a long time, need a regular maintenance according to the following tab le. Charge battery with current of 0.5C
(25A) for 1 hour when maintenance.
Storage parameters under different storage conditions-1
Storage environment temperature
Relative humidity of storage environment
Storage time
SOC
Below -20
℃
/
Avoid
/
-20~25
℃
5%~70%
≤
12 months
3
0%≤SOC≤60%
CAUTION:
When users need to clean the B-BOX, please switch off the system firstly.