B-BOX 12.8 installation guidance
23
/
30
3
ERROR
OFF
4
Alarm
OFF
Remark:
Slow blink: Indicator light is on and off every 1s (0.5Hz).
Fast blink: indicator light is on and off every 0.25s(2HZ)
SOC status and indicate
Item Status
Indicate
1
Four lights are all normally on
Capacity is 100%-75% (including)
2
The last three lights are normally on
Capacity is 74%-50% (including)
3
The last two lights are normally on
Capacity is 49%-25% (including)
4
The last one light is normally on
Capacity is 24%-0% (including)
ii.
Switching on the Sunny Island
Requirements:
☐
The load-break switch in the DC cable must be closed.
☐
The Sunny Island must not have
switched itself.
Procedure:
• For systems with one Sunny Island, press the "On" button on the Sunny Island. • For systems with up to three
Sunny Island inverters, press and hold the "On" button on the master
until an acoustic signal sounds.
• For multicluster systems, press and hold the "On" button on each
master until an acoustic signal sounds.
☑
The inverter LED on each Sunny Island inverter is glowing orange
and the Sunny Island inverters are in standby.
i.
Start the inverter;
Requirement:
☐
All Sunny Island inverters must be switched on.
Procedure:
• Press the start-stop button on the Sunny Island and hold it until an acoustic signal sounds.
or
Press and hold the
button on the Sunny Remote Control until an acoustic signal sounds.
☑
The inverter LED on each Sunny Island is
glowing green.