Appendix E
AC Motor Drive Settings
Page C-12
Buskro Ltd.
BK7IB-2
C.3.9 Group 8: Special Parameters.
Table C-9:
Parameters
Functions
Settings
Buskro
Setting
8-00
DC braking voltage level 0 ~ 30%
0
8-01
DC braking time during
start-up
0.0 ~ 60.0 Sec
0.0
8-02
DC braking time during
stopping
0.0 ~ 60.0 Sec
0.0
8-03
Start-point for DC braking 0.0 ~ 400.0 Sec
0.0
8-04
Momentary power loss
0: Stop operation after momentary power
loss.
1: Continues after momentary power loss,
speed search starts with master freq.
2: Continues after momentary power loss,
speed search starts with min. output
freq.
0
8-05
Max. allowable power loss
time
0.3 ~ 5.0 Sec
2.0
8-06
B.B. time for speed search 0.3 ~ 5.0 Sec
0.5
8-07
Max. speed search
current level
30 ~ 200%
150
8-08
Skip freq. 1 upper bound 0.0 ~ 400 Hz
0.0
8-09
Skip freq. 1 lower bound
0.0 ~ 400 Hz
0.0
8-10
Skip freq. 2 upper bound 0.0 ~ 400 Hz
0.0
8-11
Skip freq, 2 lower bound
0.0 ~ 400 Hz
0.0
8-12
Skip freq, 3 upper bound 0.0 ~ 400 Hz
0.0
8-13
Skip freq. 3 lower bound
0.0 ~ 400 Hz
0.0
8-14
Auto restart after fault
0 ~ 10
0
8-15
AVR function
0: AVR function enable
1: AVR function disable
2: AVR function disable when decel
2
8-16
Dynamic braking voltage
350 ~ 450V
380
8-17
DC braking lower bound
limit
0.0 ~ 400 Hz
0.0
Содержание BK7IB-2
Страница 1: ...BK7IB 2 Inline Base Part No 9105171 User s Guide V1 0 ...
Страница 5: ...General Information Buskro Ltd BK7IB Inline Base Chapter 1 1 0 General Information ...
Страница 13: ...Operator Instructions Buskro Ltd BK7IB Inline Base Chapter 2 2 0 Operator Instructions ...
Страница 22: ...BK7IB 2 Integration Buskro Ltd BK7IB Inline Base Chapter 3 3 0 BK7IB Integration ...
Страница 25: ...Electrical System Buskro Ltd BK7IB Inline Base Chapter 4 4 0 Electrical System ...