24
Q. INSTALL TRIM AND CONTROLS WITH
CARLIN ELITE EZ BURNER.
Follow instructions in Paragraph N, Steps 1 through 7.
Steam Boilers Only
(see Figures 1D and 5).
8. Connect Field Wiring
a. Steam Boiler with Hydrolevel CG450 LWCO,
Carlin Burner.
Connect
the
fi eld wiring to the pressure limit, the
LWCO, R8239C Control Center and the burner
disconnect J-box or directly to burner J-box on
burners less disconnect harness (power cord).
If equipped with tankless heater, connect fi eld
wiring from the aquastat control to the R8239C
Control Center’s “R-G” terminals. Make the
wiring connections as shown in Figure 19.
b. Steam Boiler with McDonnell & Miller
PS-801 or McDonnell & Miller 67 LWCO,
Carlin Burner.
Connect
the
fi eld wiring to the pressure limit,
the R8239C Control Center, the LWCO and
the burner disconnect J-box. If equipped with
tankless heater, connect fi eld wiring from
the aquastat control to the oil burner primary
control’s “T-T” Terminals. Make the wiring
connections as shown in Figures 20 and 21.
c. Refer to Paragraph S for details on use of burner
disconnect junction box provided with all
knockdown boiler builds.
Water boilers Only
(see Figures 1A, 1B, 1C and 5).
Follow instructions in Paragraph O, Steps 1 through 7.
9. Connect Field Wiring
a. Water boilers without tankless heater and with
front tankless heater. Connect the fi eld wiring
from the circulator to the aquastat control and
from the control to the burner disconnect J-box
or directly to oil burner primary control on
burners less disconnect harness (power cord).
Make the wiring connections as shown on
Figures 22 and 23A.
b. Water boilers with rear tankless heater. Connect
the fi eld wiring from a standard junction box
or burner disconnect J-box to the circulator,
aquastat control and burner. Make the wiring
connections as shown on Figure 23B.
c. Refer to Paragraph S for details on use of burner
disconnect junction box provided with all
knockdown boiler builds.
R. INSTALL TRIM AND CONTROLS WITH
RIELLO BURNER.
Follow instructions in Paragraph N, Steps 1 through 7.
Steam Boilers Only
(see Figures 1D and 5).
8. Connect Field Wiring
a. Steam boiler with Hydrolevel CG450 or
McDonnell & Miller 67 LWCO, Riello Burner.
Connect
the
fi eld wiring to the pressure limit,
the LWCO, R8239C Control Center and the
burner disconnect J-box or directly to oil burner
primary control on burners less disconnect
harness (power cord). If equipped with tankless
heater, connect fi eld wiring from the aquastat
control to the R8239C Control Center’s “R-G”
terminals. Make the wiring connections as shown
in Figures 19 and 21.
b. Steam boiler with McDonnell & Miller PS-801
LWCO, Riello Burner.
Connect
the
fi led wiring to the pressure limit,
the R8239C Control Center, the LWCO and the
burner J-box. If equipped with tankless heater,
connect fi eld wiring from the aquastat control to
the R8239C Control Center’s “R-G” terminals.
Make the wiring connections as shown in Figure
20.
c. Refer to Paragraph S for details on use of burner
disconnect junction box provided with all
knockdown boiler builds.
Water Boilers Only
(see Figures 1A, 1B, 1C and 5).
Follow instructions in Paragraph O, Steps 1 through 7.
9. Connect Field Wiring
a. Water boilers without tankless heater and with
front tankless heater. Connect the fi eld wiring from
the circulator to the aquastat control and from the
control to the burner disconnect J-box or directly
to oil burner primary control on burners less
disconnect harness (power cord). Make the wiring
connections as shown on Figures 22 and 23A.
b. Water boilers with rear tankless heater. Connect the
fi eld wiring from a standard junction box or burner
disconnect J-box to the circulator, aquastat control
and burner. Make the wiring connections as shown
on Figure 23B.
c. Refer to Paragraph S for details on use of burner
disconnect junction box provided with all
knockdown boiler builds.
S. BURNERS SUPPLIED BY BURNHAM
utilize
a burner disconnect harness that is pre-wired into the
burner junction box and primary control. Packed in the
canopy carton is the mating burner disconnect junction
assembly and mounting hardware for use with these
burners.
If you are using a burner with the disconnect harness,
complete the following assembly instructions for
mounting the mating burner disconnect junction box,
see Figure 10.
Содержание V8 Series
Страница 6: ...6 Figure 1A V82 thru V89 Water Boiler without Tankless Heater ...
Страница 7: ...7 Figure 1B V83 thru V89 Water Boiler with Front Tankless Heater ...
Страница 8: ...8 Figure 1C V83 thru V89 Water Boiler with Rear Tankless Heater ...
Страница 9: ...9 Figure 1D V83 thru V89 Steam Boiler with or without Tankless Heater ...
Страница 27: ...27 Figure 11B Top View Burner Swing Door Mounted to Cast Iron Block Assembly Jacket Removed for Clarity ...
Страница 33: ...33 Figure 13A Recommended Water Piping for Circulator Zoned Heating System ...
Страница 34: ...34 Figure 13B Recommended Water Piping for Zone Valve Zoned Heating System Supply Side Circulator ...
Страница 35: ...35 Figure 13C Recommended Water Piping for Zone Valve Zoned Heating System Return Side Circulator ...
Страница 46: ...46 Figure 19A Wiring Diagram Steam Hydrolevel CG450 Probe LWCO for Carlin Burners ...
Страница 47: ...47 Figure 19B Wiring Diagram Steam Hydrolevel CG450 Probe LWCO for Riello Burners ...
Страница 49: ...49 Figure 20A Wiring Diagram Steam McDonnell Miller PS 801 Probe LWCO for Carlin Burners ...
Страница 50: ...50 Figure 20B Wiring Diagram Steam McDonnell Miller PS 801 Probe LWCO for Riello Burners ...
Страница 52: ...52 Figure 21A Wiring Diagram Steam McDonnell Miller 67 Float LWCO for Carlin Burners ...
Страница 53: ...53 Figure 21B Wiring Diagram Steam McDonnell Miller 67 Float LWCO for Riello Burners ...
Страница 55: ...55 Figure 22A Wiring Diagram Water without Tankless Heater for Carlin Burners ...
Страница 56: ...56 Figure 22B Wiring Diagram Water without Tankless Heater for Riello Burners ...
Страница 58: ...58 Figure 23B Wiring Diagram Water with Front Tankless Heater for Carlin Burners ...
Страница 59: ...59 Figure 23C Wiring Diagram Water with Front Tankless Heater for Riello Burners ...
Страница 62: ...62 Figure 23F Wiring Diagram Water with Rear Tankless Heater for Riello Burners ...
Страница 82: ...82 Bare Boiler Assembly ...
Страница 84: ...84 Bare Boiler Assembly Continued ...
Страница 86: ...86 Jacket Assembly ...
Страница 88: ...88 V83 Thru V89 Steam Boilers Trim and Controls ...
Страница 90: ...90 V82 Thru V89 Water Boilers Trim and Controls ...
Страница 92: ...92 Beckett AFG Burner ...
Страница 98: ...98 SERVICE RECORD DATE SERVICE PERFORMED ...