Figure 12: Gas Valve Pressure Tap

3. For natural gas fi red boiler, temporarily turn off all 

other gas-fi red appliances.

E.

  Follow Operating Instructions

 to place boiler in 

operation. See Figure 17.

F.

  Sequence of Operation.

 See Figure 14. If boiler fails 

to operate properly, see Troubleshooting Tree on pages 
20-22.

G.

  Check gas piping and connections

 between Gas Valve 

and Manifold, Orifi ces and Pilot Tubing. Use soap 
solution or other approved method. See Figure 13.

Figure 13: Schematic Pilot and Gas Piping

Figure 11: Main Burner Installation

VII. System Start-up

A. 

 Safe operation

 and other performance criteria were 

met with gas manifold and control assembly provided 
on boiler when boiler underwent tests specifi ed in 

American National Standard for Gas-Fired Low-
Pressure Steam and Hot Water Boilers,

 ANSI Z21.13.

B.

 

Fill heating system with water

 and vent air from 

system. Use the following procedure on a Series Loop 
System equipped with zone valves. See Figure 3.

1.  Close isolation valve in boiler supply piping.

2.  Isolate all circuits by closing zone valves or 

balancing valves.

3.  Attach hose to hose bib located just below isolation 

valve in boiler supply piping. Terminate hose in fi ve 
gallon bucket at a suitable fl oor drain or outdoor 
area).

4.  Starting with one circuit, open zone valve.

5.  Open hose bib.

6. Open fi ll valve. Makeup water line should be 

located directly above isolation valve in boiler 
supply piping.

7.  Allow water to overfl ow from bucket until discharge 

from hose is bubble free for 30 seconds.

8.  Open zone valve to second zone to be purged, then 

close fi rst. Repeat this step until all zones have been 
purged, but always have one zone open. At 
completion, open all zone valves.

9.  Close hose bib, continue fi lling system until pressure 

gauge reads 12 psi. Close fi ll valve.

 

Note: If makeup water line is equipped with 
pressure reducing valve, system will automatically 
fi ll to 12 psi. Leave globe valve open.

10. Open isolation valve in boiler supply piping.

11. Remove hose from hose bib.

C. 

Check main burners.

 See Figure 11. Rear of burner 

must be in vertical slot in rear of burner tray. Front of 

burner must be seated on orifi ce.

D. 

Prepare to check operation.

1.  Obtain gas heating value (in Btu per cubic foot) 

from gas supplier.

2.  Connect manometer to pressure tap on gas valve. 

See Figure 12.

Содержание 2PV Series

Страница 1: ...r e S d n a r e b m u N l e d o M r e l i o B e d i v o r p r e l i o b r e b m u N l e d o M r e l i o B _ _ _ _ I _ V P _ 0 2 r e b m u N l a i r e S r e l i o B _ _ _ _ _ _ _ 6 e t a D n o i t a l...

Страница 2: ...t u p n i s a g e c u d e r o t d e c i f i r o y l l a i c e p s n e e b F x i d n e p p A d n a 2 1 8 n o i t c e S 1 3 2 2 Z I S N A 4 5 A P F N e d o C s a G l e u F l a n o i t a N e h t r e p r...

Страница 3: ...n o i s n e m i D t n e t n o C r e t a W s n o l l a G g n i p p i h S x o r p p A b l t h g i e W A B C D V P 3 0 2 0 2 4 1 6 1 1 0 1 8 5 5 1 2 3 5 6 2 V P 4 0 2 3 2 7 1 1 1 8 5 5 1 4 9 0 3 V P 5 0...

Страница 4: ...s s a o t d e d i v o r p e b t s u m n o i t s u b m o c The following guideline is based on the National Fuel Gas Code NFPA 54 ANSI Z223 1 1 Determine volume of space boiler room Rooms communicatin...

Страница 5: ...al space s of sufficient volume such that combined volume of all spaces meet criteria for unconfined space Size each opening for minimum free area of 1 square inch per 1 000 Btu per hour input of all...

Страница 6: ...is a hot water boiler must be full of water to operate safely Refer to Section X for low water cut off piping and wiring instructions K If it is required to perform a long term pressure test of the hy...

Страница 7: ...trapped air L Oil grease and other foreign materials which accumulate in new hot water boilers and a new or reworked system should be boiled out and then thoroughly flushed A qualified water treatmen...

Страница 8: ...having jurisdiction specifies a gravity factor be applied For specific gravity greater than 0 70 apply gravity factor from Table 4 If exact specific gravity is not shown choose next higher value For m...

Страница 9: ...i c e p S y t i v a r G n o i t c e r r o C r o t c a F 0 5 0 0 1 1 0 3 1 7 0 1 5 5 0 4 0 1 0 4 1 4 0 1 0 6 0 0 0 1 0 5 1 0 0 1 5 6 0 6 9 0 0 6 1 7 9 0 0 7 0 3 9 0 0 7 1 4 9 0 5 7 0 0 9 0 0 8 0 7 8 0...

Страница 10: ...1 1 6 r e b m u n t r a p t i K n o i t i s n a r T t n e V A t n a l a e s f o e b u t e c n u o G N I N R A W r o c i l l a t e m n o n l e e t s s s e l n i a t s 6 1 3 e p y T r o 4 0 3 e p y T d...

Страница 11: ...e time of removal of an existing boiler the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation while the other appliances remain...

Страница 12: ...using the procedure outlined below for the Gasket Less Vent System G N I N R A W f o h t g n e l d e l l a t s n i m u m i x a m d e e c x e r e v e N e p i p h t g n e l e l b a t s u j d a r o f s...

Страница 13: ...locking band and rest against the end of the female pipe Verify the factory installed gasket is not dislodged or cut d Smooth sealant around joint for a continuous seal Reapply sealant if necessary e...

Страница 14: ...e any door window or gravity air inlet d Minimum 4 feet 6 feet in Canada horizontally from and in no case above or below unless a 4 foot horizontal distance is maintained from electric meters gas mete...

Страница 15: ...s II circuit between thermostat and boiler Run wires through grommet in Jacket Left Side Panel Set thermostat heat anticipator to 0 6 amps See Figure 10 D Wire boiler Boiler is rated for 120 VAC 60 he...

Страница 16: ...one valves or balancing valves 3 Attach hose to hose bib located just below isolation valve in boiler supply piping Terminate hose in five gallon bucket at a suitable floor drain or outdoor area 4 Sta...

Страница 17: ...ame should have clearly defined inner cone with no yellow tipping Orange yellow streaks should not be confused with true yellow tipping Figure 16 Main Burner Flame J Check thermostat operation Raise a...

Страница 18: ...ifold pressure Do not reduce more than 0 3 inch w c If boiler is still overfired contact your Burnham distributor or Regional Office for replacement Gas Orifice b Increase input rate if less than 98 o...

Страница 19: ...19 Figure 17 Operating Instructions...

Страница 20: ...20...

Страница 21: ...21...

Страница 22: ...22...

Страница 23: ...ve gear 1 A National Institute for Occupational Safety and Health NIOSH approved respirator 2 Long sleeved loose fitting clothing 3 Gloves 4 Eye Protection Take steps to assure adequate ventilation Wa...

Страница 24: ...examine all flue passageways a If passageways are free of soot and obstruction replace canopy secure and seal using kit available from Burnham Distributors Part No 6111716 b If passageways need clean...

Страница 25: ...screws holding pilot burner to pilot bracket b Disconnect pilot tubing c Disconnect all other leads to pilot d Select pilot assembly with identical model number reconnect leads and pilot tubing Resecu...

Страница 26: ...Pressure 3 Start boiler and read pressure on manometer when boiler water temperature reaches operating temperature Refer to Table 8 for minimum readings NOTE If switch drops out before boiler reaches...

Страница 27: ...o m m o C 0 1 D 2 x e H y v a e H 0 2 t u N e r a w d r a H n o m m o C 2 E 2 F 2 o N y e K n i d e d u l c n I t e k s a G g n i t n u o M r e w o l B 8 4 0 6 0 2 8 1 9 4 0 6 0 2 8 1 F 2 r e w o l B...

Страница 28: ...1 D 3 y a r T r e n r u B 5 0 3 0 0 6 8 1 7 1 5 0 4 0 0 6 8 1 7 1 5 0 5 0 0 6 8 1 7 1 5 0 6 0 0 6 8 1 7 1 E 3 y l b m e s s A g e L e s a B 1 0 0 6 8 1 6 4 1 E 3 g e L e s a B 1 2 0 0 6 8 1 7 4 2 E 3...

Страница 29: ...3 4 0 0 6 2 2 8 1 3 5 0 0 6 2 2 8 1 3 6 0 0 6 2 2 8 1 l a r u t a N D 4 y l n O s a G k n i P 5 4 e c i f i r O r e n r u B n i a M 1 1 7 2 2 8 3 1 1 7 2 2 8 5 1 1 7 2 2 8 7 1 1 7 2 2 8 9 D 4 e n a p...

Страница 30: ...P A 5 o N y e K h t i w d e d u l c n I P K 6 4 1 8 8 3 l l e w y e n o H e n a p o r P P L e c i f i r O t o l i P C 5 T P N x D O 8 1 g n i t t i F t u N n o i s s e r p m o C E 5 d n a A 5 o N y e...

Страница 31: ...0 7 1 4 0 6 1 E 6 r o o D e l b a v o m e R t n o r F t e k c a J 4 4 3 0 7 1 4 0 6 1 4 4 4 0 7 1 4 0 6 1 4 4 5 0 7 1 4 0 6 1 4 4 6 0 7 1 4 0 6 1 F 6 l e n a P t n o r F r e w o L t e k c a J 3 1 3 0...

Страница 32: ...32...

Страница 33: ...0 6 1 0 6 1 1 E 7 V P 4 0 2 3 0 2 g n o L 2 1 x D I 6 1 3 g n i b u T e n o c i l i S h t g n e L y f i c e p S 7 0 0 6 1 0 9 V P 5 0 2 g n o L 3 1 x D I 6 1 3 g n i b u T e n o c i l i S V P 6 0 2 g...

Страница 34: ...y t i t n a u Q V P 3 0 2 V P 4 0 2 V P 5 0 2 V P 6 0 2 n o t r a C y r o s s e c c A t n e V d e t e k s a G 8 3 2 3 0 7 1 1 1 6 3 2 5 0 7 1 1 1 6 A 8 r o t c e n n o C t n e V 6 0 3 6 1 1 8 1 7 0 3...

Страница 35: ...o connect the probe LWCO to the supply or return piping as shown below LWCO Location draining the heating system Many probe LWCO manufacturers recommend an annual inspection of the probe How to Wire L...

Страница 36: ...l remedies in the courts THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS AND YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE Limited Warranty FOR RESIDENTIAL CAST IRON WATER BOILERS 03 03...

Отзывы: