Installation / Service / User Manual

                                                                          BURNERTECH 

 
 

20 

 

6.3 

Fault Finding

 

 

6.3.1 

Lockouts/Blockings 

 
Several checks are included to protect the boiler and its environment. High limit switch is constantly 
monitored, safety times are constantly compared etc. 
Any violation of (programmable) limits (and/or internal thermostat functions) will lead to an 
error/fault or warning condition. The fan will not operate if there is a lockout or blocking condition. 
 

6.3.1.1

 

Lock-out reset 

 
Severe error will cause a lockout condition which can be cleared by pressing the reset button on the 
control. In case of lockout and blocking conditions, Fan will not operate. Blocking error will be 
resolved automatically if the cause of the error disappeared. 
 
Error codes / Faults can be divided in two groups: 

 

Lock-out condition codes 

 

Blocking condition codes 

 

Complete list of errors of the controller is given in the following table: 

 

NOTE:

 

The Error / Fault codes are visible only through a PC interface

 

 

 

ERROR 

CODE 

DESCRIPTION 

CAUSE AND POSSIBLE SOLUTION 

LOCK-OUT ERRORS 

01 

Flame lockout 
after several 
ignition trials

 

Lockout signal after no flame and all ignition trials are expired. This error 
condition is stopping the boiler from running. To get to the normal 
operation again, manual/remote reset is required. By using the local 
reset key, number of resets are not limited. However, all remote resets 
(communication) are limited to 5 resets per hour. 

02 

False Flame 
Indication 

Error is created if flame current is detected in illegal situations (no heat 
demand currently present, gas valve closed, safety time passed). This 
error condition requires manual reset action. 
 

03 

High Limit error 

High Limit error is created if the safety cut-off switch opens due to an 
overheat situation in the application, 
 

04 

APS related Errors 

 

If the APS is configured and the APS does not open or close within the 
configured time limits Error 4 is generated. If the APS is not configured 
but an APS switch is detected on the input Error 4 is also generated. 

05 

Fan Tacho signal 
error 

If the measured fan speed is not within 900 RPM of the requested fan 
speed in 20 seconds, error will be generated 

08 

Flame circuit error 

During normal operation of the ignition controller, flame circuit is 
regularly checked. This check has predictable behaviour and several 
steps. If check fails, error 8 will be set. 

09 

Gas valve driver 
circuit error 

During normal operation of the ignition controller, valve drive circuit is 
regularly checked. This check has predictable behaviour and several 
steps. If check fails, error 9 will be set. 

13 

Remote reset 
lockout (volatile) 

All remote resets (communication) are limited to 5 resets per hour. If the 
limit is exceeded, Volatile lockout error is set; the error disappears after 
power off/on the boiler. 

21 

ADC error 

Internal controller error. 

25 

CRC error 

Matching error on CRC codes (different software versions). 

BLOCKING ERROR 

34 

Low Mains Voltage

 

Low Mains voltage (less than 150 +/- 10 VAC) will trigger this error. 
When Mains brought back (VAC), error is resolved in 10 seconds. 

 
 
 

Содержание INVERTERJET 30M/L

Страница 1: ...bject to Modifications MODEL PRODUCT CODE CLASS INVERTERJET 30M L 91353 MODULATING PRE MIX BURNER INVERTERJET 30M N 91354 MODULATING PRE MIX BURNER INVERTERJET 50M L 91320 MODULATING PRE MIX BURNER IN...

Страница 2: ...4 Commissioning 12 4 1 Commissioning procedure 12 4 1 1 Turning on the Burner 13 4 1 2 Commissioning operation 13 4 1 2 1 Maximum rate CO2 13 4 1 2 2 Minimum rate CO2 13 4 1 2 3 Burner Heat Input 13 4...

Страница 3: ...ility we advise and request that a Burnertech Approved Engineer who has attended our product course conducts the 1st burner commissioning For Training Service or Commissioning information please conta...

Страница 4: ...Installation Service User Manual BURNERTECH 3...

Страница 5: ...Max A 0 3 1 9 1 9 Gas Connection Flange Size 1 2 BSP 1 2 BSP 1 2 BSP Gas Inlet Pressure Min mbar 10 10 10 Max mbar 60 60 60 2 2 Technical Description of the Burner Parts The Burners in the Inverterje...

Страница 6: ...ght mm mm mm mm mm mm mm mm mm kg Inverterjet 30M L 89 71 91 101 6 170 133 218 361 225 5 2 Inverterjet 30M N 89 71 91 101 6 170 133 218 361 225 5 2 Inverterjet 50M L 92 71 91 101 6 170 164 244 365 238...

Страница 7: ...d ten volts can be applied to connector X3 Pins 8 16 At zero volt the fan will run on Minimum Fan speed At ten volt the fan will run on Maximum Fan speed 4 20 mA control with an external resistor of 5...

Страница 8: ...Installation Service User Manual BURNERTECH 7 3 Installation 3 1 General Installation Information...

Страница 9: ...sealing and insulating between the Mounting Plate and the bearing wall of the appliance 3 2 1 Standard Burner Mounting Detail 1 Burner Head 2 Burner Mounting Gasket 3 Boiler Door MODEL C D1 D2 G PCD...

Страница 10: ...front of the Gas connection flange at the rear of the burner 2 Check the thread on the flange and ensure that there is no debris in the threads 3 Connect the corresponding gas pipe fittings to the Gas...

Страница 11: ...Installation Service User Manual BURNERTECH 10 3 4 Electrical Installation The electrical wiring diagram for the Burners are shown in the following page 3 5 Basic Electrical Safety...

Страница 12: ...fit connector is used for communication via a dedicated Windows based PC software and USB lead Please contact Burnertech for more information An Earth must be connected to the 6 3mm spade connector on...

Страница 13: ...g procedure follow the steps bellow 1 Connect a Manometer to the gas inlet pressure test nipple on the burner gas inlet connection 2 Locate CO CO2 combustion analyser into flue pipe as close as possib...

Страница 14: ...5 CAUTION Generally the CO2 should not normally exceed 9 5 on NG or 11 on LPG We recommend that the operating CO2 is between 0 to 0 5 higher at maximum fan speed than at minimum 4 1 2 2 Minimum rate...

Страница 15: ...during a complete burner sequence The basic states are Stand by fan is off or at Continuous Fan speed when this option is selected Pre purge Ignition Run state fan speed is controlled by modulation i...

Страница 16: ...mmunication 4 1 3 1 PC USB Interface If required a windows based software along with a dedicated USB cable and driver is available to enable programming of certain parameters in the control and also t...

Страница 17: ...Installation Service User Manual BURNERTECH 16 5 User Instructions 5 1 Limitations on use of Burner...

Страница 18: ...uous Fan speed option is switched off 5 2 3 Heating Mode The normal heating mode is started when a high voltage heat demand input is closed When ignition is successful the fan can be controlled betwee...

Страница 19: ...m the chamber 6 1 1 The condition of the burner head some discolouration of the burner material is normal but the material should not be cracked or open Under no circumstances should any of the perfor...

Страница 20: ...ion The fan case has gas tight seals and the fan casing must never be opened Due to the 1 1 gas air ratio operating principle of the burner a reduction in fan performance i e dust build up will not re...

Страница 21: ...alse Flame Indication Error is created if flame current is detected in illegal situations no heat demand currently present gas valve closed safety time passed This error condition requires manual rese...

Страница 22: ...Installation Service User Manual BURNERTECH 21 6 3 2 Maintenance Notes...

Страница 23: ...Installation Service User Manual BURNERTECH 22...

Страница 24: ...C Lostock Industrial Estate Lostock Lane BL6 4BL Bolton United Kingdom Tel 44 0 1204 393222 Fax 44 0 1204 394222 Email enquiries burnertech co uk Website www burnertech co uk 99043 1 28 11 2019 Subje...

Отзывы: