26
Start-up
10.3.3 Function of the DIP switches
DIP
switches
Function
ON
DIP
1 2 3 4
1
ON
Reversal of the effective direction of the set-point
value (set-point value 20 – 4 mA corresponds to
position 0 – 100 %), descending (
DIR.CMD
)
OFF
Normal effective direction of the set-point value
(set-point value 4 – 20 mA corresponds to position
0 – 100 %), ascending
2
ON
Sealing function active. The valve completely closes
below 2 %
10)
and opens above 98 % of the set-point
value (
CUTOFF
)
OFF
No sealing function
3
ON
Correction characteristic for adjustment of the oper-
ating characteristic (linearization of the process char-
acteristic
CHARACT
)
10)
OFF
Linear characteristic
4
ON
Operating status MANUAL (MANU)
OFF
Operating status AUTOMATIC (AUTO)
Tab. 14: DIP switches