19
Electricalinstallation
9.2.2 Electrical installation 24 V DC with
circular plug-in connector
→
Connect the positioner according to the table.
6
1
7
5
4
3
2
8
Fig. 14: Circular plug M12 x 1, 8-pole
Input signals of the control center (e.g. PLC)
Pin
Wire
color
3)
Configuration External circuit / signal level
1
2
white
brown
Set-point value
+
(0/4 ... 20 mA)
Set-point value
GND
1
2
+ (0/4 ... 24 mA)
GND
5
6
grey
pink
Digital input +
Digital input
GND
5
+
0 ... 5 V (log. 0)
10 ... 30 V (log. 1)
identical to Pin 3 (GND)
Tab. 6: Pin assignment - input signals of the control center
Operating voltage
Pin
Wire
color
3)
Configuration External circuit
3
4
green
yellow
GND
+ 24 V
3
4
24 V DC ± 10 %
max. residual ripple
10 %
Tab. 7: Pin assignment - operating voltage
Output signals to the control center (e.g. PLC) - (required for
analogue output option only)
Pin
Wire
color
3)
Configuration External circuit / signal level
8
7
red
blue
Analogue
position
fe
Analogue
position
feedback GND
+ (0/4 ... 24 mA)
8
7
GND
Tab. 8: Pin assignment - output signals of the control center - option
When the supply voltage is applied, the positioner is operating.
→
Actuate the automatic adjustment of the positioner, as described
in the chapter entitled “10.2 Automatic adjustment X.TUNE”.
3)
The indicated colors refer to the connecting cable available as an
accessory (919061).
english
Type 8694
Содержание Positioner TopControl Basic 8694
Страница 82: ...82 Emballage Transport Stockage Type 8694 fran ais...