41
Start-up
ATTENTION
Breakage of the pneumatic connection pieces due to rotational impact.
▶
When opening or closing the device, do not press against the actuator, but against the basic housing.
→
Open the device: turning the transparent cap anti-clockwise.
Status indicator
(RGB LED)
ASi PWR LED (green)
ASi FAULT LED (red)
Key 2
Key 1
büS service interface
Inv.ValveDir. LED
Manual LED
Pilot LED
Figure 28:
Operating and display elements
0 s
5 s
10 s
Manual LED
Inv.ValveDir. LED
Start automatic
teach function
1
1
Status indicator
End of teach function
Figure 29:
Start automatic teach function
→
Press and hold key 1 for > 5 s to start the automatic teach function. The red manual LED and the green
Inv.ValveDir. LED flash for 5 s at 5 Hz.
→
When the red manual LED and the green Inv.ValveDir. LED start flashing faster (10 Hz), release key 1
within the next 5 s.
The status indicator flashes orange while the automatic teach function is running (function check). When
the status indicator stops flashing orange, the teach function is complete.
The end positions of the valve have been identified and saved.
Note: If the status indicator is lit red, the teach function is faulty and must be repeated.
ATTENTION
Damage or malfunction due to ingress of dirt or moisture.
To observe the degree of protection IP65 or IP67:
▶
Screw in transparent cap to the stop.
→
Close the device (see accessories for assembly tool).