39
Start-up
Invert process valve direction:
Body casing
Basic housing
Actuator
Transparent cap
Figure 24:
Open device
ATTENTION
Breakage of the pneumatic connection pieces due to rotational impact.
▶
When opening or closing the device, do not press against the actuator, but against the basic housing.
→
Open the device: turning the transparent cap anti-clockwise.
Status indicator
(RGB LED)
ASi PWR LED (green)
ASi FAULT LED (red)
Key 2
Key 1
büS service interface
Inv.ValveDir. LED
Manual LED
Pilot LED
Figure 25:
Operating and display elements
0 s
10 s
30 s
Inv.ValveDir. LED
process valve
direction
inversion
2
2
enabled
disabled
Figure 26:
Invert process valve direction
→
Keep key 2 pressed for > 10 s. The green Inv.ValveDir. LED flashes for 10 s at 10 Hz.
→
When the green Inv.ValveDir. LED flashes for a shorter time, release key 2.
The valve direction inversion is enabled: the green Inv.ValveDir. LED is lit.
The valve direction inversion is disabled: the Inv.ValveDir. LED is not lit.
NOTE
Damage or malfunction due to ingress of dirt or moisture.
To observe the degree of protection IP65 or IP67:
▶
Screw in transparent cap to the stop.
→
Close the device (see accessories for assembly tool).