16
Technical data
6.5.2.2
Electrical data, IO-Link
Protection class
III as per DIN EN 61140 (VDE 0140-1)
Connection
Supply, IO-Link
Circular plug-in connector M12 x 1, 4-pin, Port Class A
Circular plug-in connector M12 x 1, 5-pin, Port Class B
Communication
büS service interface
Operating voltage
System supply (Pin 1+3)
24 V
±25 % (according to specification)
only for Port Class B:
Actuator supply (Pin 2+5)*
24 V
±25 % (according to specification)
Current consumption
System supply (Pin 1+3)
For Port Class A max. 150 mA (only with installed pilot valves)
For Port Class B max. 50 mA
only for Port Class B:
Actuator supply (Pin 2+5)
max. 100 mA
Communication software
Bürkert Communicator
* Actuator supply is galvanically isolated from system supply in accordance with IEC 60664 and for electrical safety in accordance with
SELV from IEC 61010-2-201
6.5.2.3
Electrical data, büS
Protection class
3 as per DIN EN 61140 (VDE 0140-1)
Connection
Circular plug-in connector M12 x 1, 5-pin
Operating voltage
18–30 V
(according to specification)
Max. current consumption
120 mA @18 V (incl. inrush current pilot valve for 200 ms)
Current consumption input during
normal operation
95 mA @18 V
(after current reduction,
pilot valve after 200 ms
and 1 end position reached)
english
Type 8691 REV.3