22
Installation
8.
insTallaTion
safety instructions
8.1.
Danger!
risk of electric shock!
There is a serious risk of injury when reaching into the device.
Always disconnect the power and secure it from re-activation before removing the cover, disconnecting the
•
gears or using the lever.
Connect several rotary actuator always with phase separation via a switch!
•
Protect the rotary actuator with a mains-operated fuse!
•
Observe applicable accident prevention and safety regulations for electrical equipment!
•
Warning!
Danger - improper installation!
Improper installation may result in injuries as well as damage to the device and the area around it.
Installation may be carried out by authorised technicians only and with the appropriate tools!
•
Observe the specifications in chapter
•
.
Warning!
Danger due to unintentional activation of the device!
Unintentional activation of the device during installation may result in injuries and damage.
Take appropriate measures to prevent the device from being accidentally actuated!
•
installing the rotary actuator
8.2.
The rotary actuator is supplied with the presetting <Closed>.
The rotary actuator can be fitted to a ball valve or flap valve via the following fastening options:
ISO F05 (4 x M6 with a flange Ø of 50 mm)
•
ISO F07 (4 x M8 with a flange Ø of 70 mm)
•
ISO F10 (4 x M10 with a flange Ø of 102 mm)
•
ISO F12 (4 x M12 with a flange Ø of 125 mm)
•
english