background image

www.bullard.com

Operating the Free-Air® Pump 

1. Analyze the atmosphere at the location of the worksite, the air 

inlet and the pump, to be sure the pump will not be operating in a 
contaminated or an explosive atmosphere.

2. Make sure the pump’s inlet 

filters are located in a clean, 
uncontaminated location 
where breathable air is 
assured at all times (Figure 5).
The pump WILL NOT remove 
carbon monoxide, toxic gases 
or other contaminants from 
the incoming air it transfers to 
the respirator wearer.

3. Plug the pump into a single phase 230 or 208 volt electrical outlet. 

The pump’s motor is equipped with an 8 foot cord with three wires, 
30 amp plug (NEMA L6-30) and a manual starter.
You may use up to 50 feet of 30 amp,  
three-wires grounded extension cord to reach your electrical outlet. 
We recommend using 8 gauge wire. Avoid excessive lengths of 
extension cord, especially if running the pump continuously.

4. Assemble your respirator by following the manufacturer’s directions 

as described in the respirator’s instruction manual.
Be sure the pump’s outlet pressure, measured by the pressure 
gauge on the air supply hose attachment pod(s), will be greater 
than the minimum MSHA/ NIOSH approved pressure required 
to operate the respirator. The respirator’s minimum approved 
pressure will be found in the respirator’s user manual and/ or on 
labels attached to the respirator.
If you have any question as to whether or not your respirator is 
compatible with the pump, call the respirator manufacturer or 
Bullard’s Customer Service Department at 877-BULLARD or 
1-859-234-6616.

5. While outside of the contaminated work area, connect the air 

supply hose, that was approved by NIOSH as part of the respirator 

system being used, to the quick-
disconnect coupler(s) or the 
pod(s) (Figure 6).

NOTE

If your respirator’s air supply 
hose, approved by NIOSH 
as part of the respirator 
system being used, will not 
connect to the pod’s standard 
1/2” Industrial Interchange 
couplers, you can convert 
the couplers to 3/8” female 
NPT with installation of the 
following adaptors. 

Cat. No. V23

 - Converts one 

1/2” Industrial Interchange 
coupler to 3/8” female NPT. One 
V23 adaptor is required for each 
coupler (Figure 7).

A variety of quick-disconnect 
couplers or fittings may be used 
to connect your air supply hose to 
the 3/8” outlet adaptor. Contact 
your respirator manufacturer for 
the proper fitting (Hansen, Parker, 
Snap-Tite, Schrader, Foster, etc.) 
(Figure 8).

6. Before connecting your respirator to the air supply hose, turn the 

pump on. Allow the air to flow through the pump and hose for a few 
minutes to purge or expel any hose odors or moisture that may 
have accumulated inside the hose.

7. While outside of the contaminated work area, connect the respirator(s) 

to the air supply hose(s) using the quick-disconnect fittings.

8. With the air flowing, put on the respirator by following the 

directions in your respirator manufacturer’s instruction manual.

9. Set the pump’s outlet pressure, measured by the pressure gauge 

on the pod, to within the respirator’s approved pressure range. 
See the respirator’s instruction manual for the approved pressure 
range.

The pump has three pressure adjustment locations:

- Pressure relief valve on the pod(s) 
- Pressure relief valve on the manifold 
- Dump valve on manifold

6

Oper

ating the Fr

ee-Air Pump

 WARNING

Proper wiring in accordance with local and national electric codes 
is the responsibility of the user.

 WARNING

The respirator wearer must NOT enter the contaminated work 
area until all of the following steps have been completed.

Figure 5

Figure 8

Figure 7

Figure 6

Содержание EDP30

Страница 1: ...require expensive carbon monoxide monitors high temperature alarms or airline filters No calibration is required Read all instructions before using your Free Air pump This manual provides detailed in...

Страница 2: ...tact the respirator manufacturer or Bullard s Customer Service Department at 877 BULLARD or 1 859 234 6616 3 Supplied air respirators used with this pump MUST NOT be worn in any atmosphere immediately...

Страница 3: ...EDP30 PUMP Pump s Output Air Pressure psig Pump s Output Air Volume cfm Maximum Recommended Mask Respirators Maximum Recommended Hood Respirators Motor Amp Load 5 32 Six Four 16 10 30 Six Four 18 15...

Страница 4: ...pod s If V60 extension hose IS NOT required go to instruction 3 a Attach the V60 extension hose to the pump s manifold If extending only one pod connect the V60 hose to the manifold Kamlok coupler tha...

Страница 5: ...ry Carbon Vane 4 vanes MAXIMUM AIR PRESSURE 30 psig 15 psig AIR FLOW 30 cfm at 10 psig 50 cfm at 10 psig PRESSURE RELIEF VALVES Adjustable Pre Set to open at 34 psig when adjusted fully closed Adjusta...

Страница 6: ...f the respirator system being used to the quick disconnect coupler s or the pod s Figure 6 NOTE If your respirator s air supply hose approved by NIOSH as part of the respirator system being used will...

Страница 7: ...respirators NOTE If the pod s are attached directly to the pump manifold the pressure gauges should always read within 5 of each other If the gauge on the manifold reads substantially higher than the...

Страница 8: ...p with the gasket g Insert four 4 new filter cartridges in the seats and reassemble the caps and wing nuts to hold the cartridges in place h Reassemble the pod Tighten the wing nuts and bolts together...

Страница 9: ...ough the respirator s air supply hose until it reaches ambient air temperature 2 If pressure relief valves are set too high reset to a lower pressure Be sure the outlet pressure remains in the approve...

Страница 10: ...Gauge 0 15 psig S19683 Pressure Gauge 0 30 psig S19688 Pressure Gauge 0 60 psig S2084 Drive Belt Matched Pair EDP30 S2085 Drive Belt Matched Pair EDP50 S2089 Kamlok Adapter Male Pod S2090 Kamlok Coup...

Страница 11: ...to factory inspection In warranty product of current design will be subjected to a rehandling charge less freight originally allowed All material must be shipped with transportation charges prepaid B...

Страница 12: ...e outlet filter cartridge is multi layered with 40 micron size particles of activated carbon a sorbent bed with an exposed carbon surface of more than 15 000 square feet Vapor removal efficiency 90 95...

Отзывы: