28
Installation and maintenance instructions Logano GA124 special gas-fired boiler • Issue 04/2005
We reserve the right to make any changes due to technical modifications.
Boiler installation
7
7.6.3 Installation of the flue and combustion air pipe
Installation of the flue pipe (
Î
Fig. 27) at the boiler
z
Install condensation trap.
z
Position silicone strip approx. 1/4" wide on the boiler
intake (500 ° F-resistant silicone, use G. E. 106 or
similar).
z
Attach condensation trap to boiler connection (see
arrow) and secure with the included hose clamp.
z
Place a strip of silicone around the connection point
and smooth it to form a gas-tight connection.
Installation of the combustion air pipe at the boiler
Proceed as described above for the flue pipe to install
the combustion air pipe. A condensation trap is not
installed on the combustion air line.
Fig. 26
Condensation trap
1
Silicone strip
2
Silicone strip
3
Hose clamp
4
Condensation trap
1
2
3
4
USER NOTE
A condensation trap must always be
installed at the flue vent.
Fig. 27
Back view
1
Combustion air line connection
2
Flue gas line
1 2