10
Inspection and servicing
Logano plus GB402 – 6 720 820 700 (2018/01)
36
10.6.1 Removing and cleaning burner
▶ Undo toggle clip [1] at the top of the ventilation air hose.
▶ Pull off ventilation air hose [2] together with the connector from
ventilation air collector [3].
Fig. 44 Undoing the ventilation air hose
[1]
Toggle clip
[2]
Inlet hose
[3]
Ventilation air collector
▶ Undo the 4 screws from gas valve flange [1] and undo the gas
connection.
Fig. 45 Undoing the gas connection
[1]
Screws
▶ Undo all electrical plug-in connections at the electrode block.
Fig. 46 Undoing the electrical plug-in connections at the electrode
block
[1]
Monitoring cable
[2]
Ignition cable
[3]
Ignition cable
▶ Undo fixing nuts [1] at the top and bottom of the mixture manifold.
▶ Undo the electrical connections at the gas valve and the fan
(
▶ Carefully pull out the burner towards you.
Fig. 47 Undoing the nuts at the mixture manifold
[1]
Fixing nuts
6 720 618 585-37.2T
Содержание GB402-320-5
Страница 62: ...Logano plus GB402 6 720 820 700 2018 01 62 Notes...
Страница 63: ...Logano plus GB402 6 720 820 700 2018 01 63 Notes...
Страница 64: ......