Page 13
HOW TO LOCATE CHIMNEY EXIT AND INSTALL
Residential and Mobile Home Installation
D. Vertical Wall Exit using (6" DVL Close Clearance Pipe and elbow and any Listed 2100°
UL HT chimney and Listed 2100° UL HT T-Box assembly).
With optional pipe shield.
NOTE: For installation of optional pipe shield (See Page 23).
NOTE: For minimum clearances (See Page 14, Figure 10).
For Required Out Side Air in Mobile Homes (See Page 15).
1. Mark plumb line on wall directly behind center of heater.
(See Page 14, Figure 9).
NOTE: When using DVL Close Clearance Pipe,
maintain manufacturer’s minimum
clearances between pipe and ceiling.
2. Place vertical portion of heater pipe and elbow in position and project a point onto plumb
line level with center of elbow.
3. Measure up so there will be at least 1/4" rise per foot of horizontal connector pipe, main-
taining clearances to ceiling as noted in (Page 13, Figure 9). This will give you the center
of hole for chimney penetration.
4. After locating center of penetration, install the tee-box and chimney, per chimney
manufacturer's specifications.
5. Connect the DVL close clearance pipe to tee-box, per
manufacturer’s instructions.
DVL close clearance pipe is to be connected with (3) sheet metal screws or rivets to
connector collar on heater.(See Page 14, Figure 11).
If appliance is installed in mobile homes:
WARNING
: DO NOT INSTALL IN SLEEPING ROOMS.